4700 Specifications
30
Configuration
Modules Included
Power (Watts)
Heat Output
(BTUs)
324 ports QSFP copper
9 sFB-4700, 18 sLB-4018, 1 sFU-40H, 1
sFU-40V, 2 sMB, 3 sPSU-S
4,244W
14,479
324 ports QSFP
HyperScale Fabric Boards
9 sFB-4700x2, 18 sLB-4018, 1 sFU-40H, 1
sFU-40V, 2 sMB, 4 sPSU-S
5,279W
18,010
3.11
Maximum Heat Dissipation
Table 12: Maximum Heat Dissipation
Maximum heat dissipation
(max. for full configuration)
22,206 BTU/Hour
3.12
Airflow
Table 13: 4700 Airflow
Rated volumetric air flow for a fully configured chassis.
1300 CFM (Cubic Feet per Minute)
3.13
Physical Characteristics
Table 14: 4700 Physical Characteristics
4700 Features
Characteristics
19" rack mountable chassis
19U height
Dimensions
Width - 19" (440 mm)
Depth - 22.75" (578 mm)
Height - 25.6" (650 mm)
Weight
128 to 163 lbs (58 to 74 kg), depending on configuration
Minimum rack depth required for the rail kit
N/A
Maximum rack depth required for the rail kit
N/A
Table 15: HyperScale Physical Characteristics
HyperScale Features
Characteristics
HyperScale rack mountable chassis
20U height
3.14
Weights and Dimensions
Table 16: Weights and Dimensions
Metric (2)
English (1)
Unpacked Modules
D (cm)
W (cm)
H (cm)
Kg
D (in)
W (in)
H (in)
Lbs
Packed Modules
D
W
H
Kg
sMB-CM
33
22
4.5
1.1
13
8.7
1.77
2.42
40
28
7.5
1.4
15.7
11
3
3