Fig. 6: Unimpeded flow section
1
10 x DN
2
5 x DN
n
An unimpeded flow section of 10 x
DN (rated width) must be main-
tained before the device.
n
An unimpeded flow section of 5 x
DN (rated width) must be main-
tained after the device.
Unimpeded outlet
Fig. 7: Unimpeded outlet
If the pipe system ends at an unim-
peded outlet, the flow monitor must not
be installed directly in front of the
opening. The device must always be
completely filled with media to ensure
measuring accuracy.
Installation und initial startup
Preparatory work
03.09.2018
DWG Module BASICS Flow Monitor
31