MC200-5AM Analog I/O Module

User Manual

To reduce the chance of accident, please carefully read the operation
instructions and notes in this book prior to use. Only adequately trained
personnel shall install or operate this product. Strict compliance with the
safety rules in relevant industries, the operation instructions and safety
precautions provided in this book is required in equipment operation.

1 Port Description

1.1 Port

The extension port and user port of MC200-5AM are both protected by a
cover, as shown in Figure 1-1. Removing the covers reveals the extension
port and user port, as shown in Figure 1-2.

P

O

W

ER

24

V

R

UN

EC

20

-5

AM

Extension cable

Extension port cover

 User port cover

26

2

25

P

O

W

E

R

24

V

R

UN

EC

20

-5 AM

10

2

4

6

8

20

12 14

16 18

9

1

3

5

7

19

11

13 15 17

V2+

24V-

V1+

I1+

24V+ FG

VI2-

I2+ I3+

VI3-

V4+ I4+ VO+ IO+

User port

Extension port

Extension cable

VI1-

V3+

VI4-

VIO-

Figure 1-1 MC200-5AM appearance

Figure 1-2 Module ports

The extension cable connects MC200-5AM to the system, while the
extension port connects MC200-5AM to another extension module of the
system. For details on connection, See

1.2 Connecting Into System.

The user port of MC200-5AM is described in Table 1-1.

Table 1-1 MC200-5AM user port description

Terminal Name

Description

Terminal Name Description

1

24V+

Analog power supply
24V+

11

V3+ CH3 voltage input

2

24V-

Analog power supply
24V-

12

I3+ CH3 current input

3

FG Shielding ground

13

VI3- CH3 common GND

4

PG Protection ground

14

V4+ CH4 voltage input

5

V1+ CH 1 voltage input

15

VI4- CH4 common GND

6

I1+ CH 1 current input

16

I4+ CH4 current input

7

VI1- CH1 commond GND

17

·

NC

8

V2+ CH2 voltage input

18

VO+ Voltage output

9

VI2- CH2 commnd GND

19

VIO-

Output channel
common GND

10

I2+ CH2 current input

20

IO+ Current output

Note:

An input channel cannot receive both voltage signals and current

signals at the same time. If you intend to use a channel for current
measurement, short its voltage input terminal and current input terminal.

1.2 Connecting Into System

Through the extension cable, you can connect MC200-5AM to MC200 series
basic module or other extension modules. While through the extension port,
you can connect other MC200 series extension modules to MC200-5AM. See
Figure 1-3.

Basic module

Extension module

Removing extension port cover

before connection

Extension cable

Figure 1-3 Connecting into system

1.3 Wiring

Figure 1-4 shows the wiring of the user port.

I1+

CH1

24 V+

24 V-

DC /DC

converter

AGND

+

5V

-

5 V

PG

N

D

EC

20

-

5AM

24

 V

dc

±

10

%

60

m

A

V1+

VI 1-
FG

AGND

250

130

K

130

K

390

K

390

K

AGND

Current input

I4+

CH4

V4+

VI 4-
FG

AGND

250

130

K

130

K

390

K

390

K

AGND

Voltage input

Load

CHO

IO+

VO+

VIO -

AGND

Figure 1-4 Wiring of MC200-5AM user port

The circled 1 ~ 9 stands for the nine points to be observed during wiring.
1. It is recommended to use shielded twisted pair for the analog input and
output and separate them from power cables and any cable that may
generate EMI.
2. If the I/O signal has electric noise or voltage fluctuation, it is advisable to
connect a smoothing capacitor (0.1µF ~ 0.47µF/25V).
3. If strong EMI exists, connect the FG terminal to the PG terminal.
4. Each load of the PLC should be grounded separately

5. If a channel is used for current input, short its voltage input terminal and
current input terminal.
6. Shorting the voltage output terminals or connecting current load to voltage
output terminals may damage MC200-5AM.
7. Properly ground the module’s PG terminal.
8. The basic module’s 24Vdc auxiliary power or other qualified external
power supply can be used as the power source of the module’s analog
circuit.
9. Do not use the NC terminal.

2 Indices

2.1 Power Supply

Table 2-1 Power supply

Item

Description

Analog circuit

24Vdc (-15%~20%), maximum allowable ripple voltage
5%, 90mA (from basic module or external power supply)

Digital circuit

5Vdc, 50mA (from basic module)

2.2 Performance

Table 2-2 Performance

Item

Index

Conversion
speed

AD conversion

15ms/channel (normal)
8ms/channel (high speed)

DA conversion 6ms/channel (max.)

Analog
input

Voltage

-10 ~ 10Vdc (input impedance 200kΩ)

Warning: this module may be damaged if
the input voltage exceeds ±15Vdc

Current

-20~20mA (input impedance 250Ω)

Warning: this module may be damaged if
the input current exceeds ±32mA

Analog
output

Voltage

-10~10Vdc (external load impedance ≥ 2kΩ)

Current

0~20mA (external load impedance ≤ 520Ω)

Digital output

Default: -2000 ~ 2000
Setting range: -10000 ~ 10000

Digital input

Default: -2000 ~ 2000
Setting range: -10000 ~ 10000

Resolution

Voltage input

5mV

Current input

10µA

Voltage output 5mV
Current output 10µA

Accuracy

Analog input

±1% of full range

Analog output ±1% of full range

Содержание MC200-5AM

Страница 1: ...es to MC200 5AM See Figure 1 3 Basic module Extension module Removing extension port cover before connection Extension cable Figure 1 3 Connecting into system 1 3 Wiring Figure 1 4 shows the wiring of the user port I1 CH1 24 V 24V DC DC converter AGND 5V 5 V PGND EC 20 5AM 24 Vdc 10 6 0mA V1 VI 1 FG AGND 250 130K 130K 390 K 390 K AGND Current input I4 CH4 V4 VI 4 FG AGND 250 130K 130K 390 K 390 K ...

Страница 2: ...parameter abnormal or setting error Deviation gain normal b2 power supply failure 24Vdc power supply failed Power supply normal b3 hardware fault AD converter hardware faulty Hardware normal b10 digital range error 1 Digital output after AD conversion outside the range of 2048 2047 2 Digital input for DA conversion outside specified range Digital input output value normal b11 average sampling erro...

Страница 3: ...nput 0V outputs 0 Analog input 1V or 4mA outputs 0 Analog input 10V outputs 10 000 Analog input 5V or 20mA outputs 3000 Figure 3 3 Changing input channel characteristics 3 2 Setting Analog Output Channel Characteristics The analog output channel characteristic of MC200 5AM is the linear relationship between the channel s analog output A and digital input D It can be set by the user Each channel ca...

Страница 4: ...ply possibly faulty or MC200 5AM faulty The status of the RUN indicator Flash quickly MC200 5AM in normal operation Flash slowly or OFF Check the information in BFM 300 Notice 1 The warranty range is confined to the PLC only 2 Warranty period is 18 months within which period Megmeet Network Power conducts free maintenance and repairing to the PLC that has any fault or damage under the normal opera...

Отзывы: