background image

 

 

MCCV6000-18 Guide

 

85240 Rev 3 January 2017 

GENERAL 

The MCCV6000-18 is a flexible multi-range, 
auto identifying current clamp meant for 
operation with the Megger Power Quality Line 
of Instruments. This current clamp will measure 
AC current up to 6000Aac. This CT is powered 
by the Megger line of Power Quality 
Instruments. 

SAFETY and SYMBOLS 

 

WEEE 

The crossed out wheeled bin placed 
on Megger products is a reminder 
not to dispose of the product at the 
end of its life with general waste.

 

Megger

 

is registered in the UK as a 

Producer of Electrical and 
Electronic Equipment. The 
Registration No is WEE/DJ2235XR. 

 

Equipment complies with current 
EU directives.

 

 

Application around or removal from 
hazardous live conductors is 
permitted. 

 

Equipment protected throughout by 
double insulation. 

CAUTION

 

is defined as a condition 

or practice which could result in 
damage to or destruction of the 
equipment or apparatus under test. 

WARNING is defined as a condition 
or practice which could result in 
personal injury or loss of life. 

Safety warnings are precautions that must be 
read and understood before the instrument is 
used. They must be observed during use. 

Do not leave the instrument connected to the 
system under test when not in use. 

Always use extreme caution when connecting 
the instrument around bare conductors, under 
fault conditions, high voltage or currents may 
be present and may pose a shock hazard. 

Personal protective equipment (PPE) must be 
used during the installation and removal of this 
instrument from hazardous live connectors. 

Do not touch circuit connections or any metal 
that is exposed due to damaged insulation. 

Do not use the instrument or connect it to any 
external system if it shows any visible signs of 
damage, malfunction or if it has been stored in 
unfavorable conditions. 

Always inspect the instrument prior to use.  

Replace any defective parts or return the 
instrument to an authorized center for repair. 

Do not use the instrument or connect it to any 
external system if the enclosure is open or any 
parts of the enclosure are missing. 

The instrument shall not be used if any parts 
are damaged. 

This instrument is not intrinsically safe and 
must not be used in hazardous atmospheres. 

If this equipment is used in the manner not 
specified by the manufacturer, the protection 
provided by the equipment may be impaired. 

SPECIFICATIONS 

Max Voltage: 1000V to Ground 

The instrument is not suitable for measuring 
DC currents. 

Current Range:

5 – 60AAC RMS 

Scale at 60A 

16.7mV / Amp 

Current Range:

60 – 600AAC RMS 

Scale at 600A 

1.67mV / Amp 

Current Range:

600 – 3000AAC RMS 

Scale at 3000A 

0.33mV / Amp 

Current Range:

1500 – 6000AAC RMS 

Scale at 6000A 

0.167mV / Amp 

Bandwidth:  

20 Hz to 5 kHz 

Accuracy:  

1% of reading @ 50/60Hz 

Phase Shift:  

< 0.7

 max @ 60A 

Phase Shift: 

< 0.4

 max @ 600A 

Phase Shift: 

< 0.4

 max @ 3000A 

Phase Shift: 

< 0.4

 max @ 6000A 

Overload:  

20KA Continuous 

Power Source: 

PQ Instrument 

ID: 

7 inches (18.0cm) 

Length:  

Total Cable Length 
6 feet (182.8cm) 

Weight:  

10 oz (283g) 

Operating 
Temperature: 

-20 – 50C 

Storage 
Temperature: 

 -40 – 70C 

Humidity:  

95% NC 

Altitude:  

2000 meters 

 

 