9.3 Running a
measurement
Running a single close (C) or open
(O) operation
1]
Connect the breaker as described in section
9.1 above.
2]
Run a breaker operation without measure-
ment by turning the OPERATE knob. This
tests the connection. Run the operation with
measurement by turning the MEASURE knob.
Running an Open-Close-Open
(O-C-O) operation
1]
Connect the breaker as described in section
9.1 above.
2]
Select O-C-O (open-close-open) operation
in the SEQUENCE menu by using the arrow
keys.
3]
Press
ENTER
to set the close and open delay
values. The default value is 300 ms (0.30 s) for
close pulse delay and 10 ms (0.01 s) for open-
ing pulse delay. Press
ENTER
to continue.
4]
Set the pulse length values if needed. Press
ENTER
to confirm your settings.
5]
Run a breaker operation without measure-
ment by turning the OPERATE knob. This
tests the connection. Run the operation with
measurement by turning the MEASURE knob.
Note
The first measurement must be a single close or
open operation.
9.4 Reading the printouts
For more information about the printer, see Chapter
12 (The printer).
The first part of the printout shows administrative
data and test conditions.
The second part of the printout shows the result in
numeric and graphic form.
you can also view the results on the display if you
activate the DISPLAy option on the MAIN menu.
Option - End
BM0087OE
ZP-BM01E
EGIL
53
9 HOW TO MAkE A MOTION MEASUREMENT (OPTION)
Содержание EGIL
Страница 1: ...WWW MEGGER COM User s Manual EGIL Circuit Breaker Analyzer Art No ZP BM01E Doc BM0087OE V04a 2015...
Страница 2: ......
Страница 9: ...BM0087OE ZP BM01E EGIL 9 2 Introduction...
Страница 11: ...BM0087OE ZP BM01E EGIL 11 3 Quick instructions...
Страница 17: ...BM0087OE ZP BM01E EGIL 17 5 Description...
Страница 20: ...6 Control panel 20 EGIL ZP BM01E BM0087OE 6 Control panel...
Страница 40: ...40 EGIL ZP BM01E BM0087OE 7 Menu options and parameter settings...
Страница 41: ...BM0087OE ZP BM01E EGIL 41 7 Menu options and parameter settings...
Страница 42: ...42 EGIL ZP BM01E BM0087OE 7 Menu options and parameter settings...
Страница 43: ...BM0087OE ZP BM01E EGIL 43 7 Menu options and parameter settings...
Страница 45: ...BM0087OE ZP BM01E EGIL 45 8 How to make a time measurement...
Страница 49: ...BM0087OE ZP BM01E EGIL 49 9 How to make a motion measurement option...
Страница 63: ...BM0087OE ZP BM01E EGIL 63 14 Specifications...
Страница 67: ...BM0087OE ZP BM01E EGIL 67 14 Specifications...
Страница 70: ...70 EGIL ZP BM01E BM0087OE Index...
Страница 71: ...BM0087OE ZP BM01E EGIL 71 Index...