Setting up Fixtures, Test Accessories, and Lead Connections
58 Baker DX 71-030 User Guide EN V10
www.megger.com
Connecting High-voltage Leads to a Motor
NOTE: Before you connect leads to a motor for any test, collect information about the motor you want to test
(for example, motor name plate information). We highly recommend you do this to efficiently set up the test
and to ensure you compile accurate test records, but of course you will also need part of the information to
determine test voltages needed.
High-voltage leads are used during DC and Surge testing. The connections described here are
for three-phase testing mode.
1.
Ensure motor leads are properly labeled to provide accurate test data.
2.
Connect the high-voltage test leads to each of the motor leads. Motor lead 1 connects
to test lead 1, motor lead 2 connects to test lead 2, and motor lead 3 connects to test
lead 3.
3.
Connect the ground cable to motor ground.
4.
Ensure test/motor leads do not contact each other or the motor chassis during testing.
Figure 63. Connecting high-voltage test leads to motor leads.
Содержание Baker DX
Страница 1: ......
Страница 2: ......
Страница 10: ...Table of Contents viii Baker DX 71 030 User Guide EN V10 www megger com...
Страница 28: ...Baker DX Instrument Overview 18 Baker DX 71 030 User Guide EN V10 www megger com...
Страница 38: ...Baker DX User Interface Overview 28 Baker DX 71 030 User Guide EN V10 www megger com...
Страница 58: ...Setting up the Baker DX Tester 48 Baker DX 71 030 User Guide EN V10 www megger com...
Страница 149: ...megger com 139 RIC Templates Figure 141 RIC template 1...
Страница 150: ...RIC templates 140 Baker DX 71 030 User Guide EN V10 www megger com Figure 142 RIC template 2...
Страница 155: ...Index megger com 145...
Страница 156: ...megger com 146...