Automatic DC Test
During Automatic DC testing, you can use the toggles below the graph to display or hide Y-axis elements for current
and resistance. Otherwise, all testing is automatically executed from this screen using the parameters specified in the
active test configuration of the selected asset.
NOTE: Use the E-STOP button on the lower right of the ADX front panel to stop the test and quickly de-
energize the high-voltage leads if needed.
Notice that this screen has only a START/STOP button in place of all the controls available in manual mode.
After pressing START, voltage is applied to the test leads automatically by the ADX. The LEADS ENERGIZED indicator
in the top right corner flashes until the leads have properly discharged. LEDs on the ADX front panel also light when
leads are energized.
You can monitor test progress, viewing applied voltage along with current and resistance values as the test executes.
The software adds markers to key points in the test process where IR, DA, and PI testing complete. Markers also
appear for HiPot tests.
If a test fails during this process, the software will provide a message notifying you of the issue and will terminate
the test immediately. In the event of a failure, stop testing and evaluate the test data before conducting any further
troubleshooting or testing.
Fig 108:
Auto DC Test screen running Standard Hipot Test.
www.megger.com
Megger Baker ADX User Guide
110
Auto Tests
Содержание ADX15
Страница 1: ...Megger Baker ADX Automated Diagnostic Test Equipment User Guide...
Страница 2: ...www megger com Megger Baker ADX User Guide...
Страница 10: ...www megger com Megger Baker ADX User Guide viii Table of Contents...
Страница 44: ...www megger com Megger Baker ADX User Guide 34...
Страница 84: ...www megger com Megger Baker ADX User Guide 74 Routes...
Страница 148: ...www megger com Megger Baker ADX User Guide 138...
Страница 172: ...www megger com Megger Baker ADX User Guide 162...