MegaLife SS100F Скачать руководство пользователя страница 1

Touch Screen Room Thermostat

User Guide

Model

SS100F

Welcome

Your new thermostat will provide year of reliable service.

Using this digital thermostat will provide more uniform

comfort in your home through the seasons. Thank you for

buying the product!

Please read this manual for complete instructions on

installing and operating your thermostat. If you require further

assistance, please feel free to contact us.

In the box you will find

Thermostat

1pc

Screws

2pc

User Guide

1pc

Wall plate

1pc

Service

We offer the warranty of 18 months from the sales day. If it is

not the problem of quality or beyond the warranty time, we

will charge for the after-sale service.

Technical Data of your thermostat

Sensor

NTC

Accuracy

±0.5

Temp. Range

5 -35

Power Consumption

<1.5W

Timing error

<1

Power Supply

100~230VAC, 50

~60Hz

Current Load

5A for fan and 3A for valve

Shell Material

PC+ABS

Fireproof

Dimension

86x86x13.3mm

Installation box

86*86mm or European 60mm

Ambient Temp.

0 ~ 45

℃,

5 ~ 95

RH(Non condensing

Storage Temp

-5~ 55

About your thermostat

SS100F

series Modern Touch Screen Room Thermostats

are designed to on/off control the fans and valves in air

conditioner applications via comparison of the room

temperature and setting temperature as reaching the aim of

comfort and saving energy. SS100F are microprocessor

based thermostat with LCD display.

Features of your thermostat

Modern design similar as a cell phone.

Acrylic lenses to avoid the finger scrath. Touch Button makes

simple operation.

Large screen display with backlight is easy to read—even in

the dark.

Four periods program schedules maximize comfort and

economy.

One-touch temp control overrides program schedule at any

time.

Precise comfort control keeps temperature within 0.5°C of

the level you set.

Easy installation.

86mm hidden box and european 60mm round box is

available.

Home screen quick reference

Model definition of your thermostat

A1: Two pipe; Control Fan Coil Unit and Two wired Motorized

valve.(when room temperature reaches the setpoint, both will

turn off)

A2: Two pipe; Control Fan Coil Unit and Two wired Motorized

valve.(when room temperature reaches the setpoint, valve will

turn off but fan will turn to low speed)

B: Two pipe; Control on/off Motorized Damper C: Two Pipe;

Control Fan Coil Unit and Three wired Motorized valve

M: Two pipe; Control 0-10V Motorized Valve

E: Four pipe; Control Fan Coil Unit and Two wired Heat and Cool

Motorized valve.

T: Clock

L: Backlight

P: Weekly Programmable

N: RS485/MODBUS RTU communication K: Keycard

E: External sensor

P and N could not be compatible at the same time.

For example: SS100FA1LN

Operation

1. Setting the temperature

In the programming mode, time and timing on/off could not be

adjusted. the set temperature can be adjusted temporarily only,

If the user want to change the timing and temperature, please

reprogram.
In the manual mode, press

or

to set temperature.

will

display in the screen.

2. Setting Lock (optional function)

Press and hold

and

for 5 sec. to lock the screen. The icon

will display on the screen.

Press and hold

and

again for 5 sec. to unlock the screen.

3. Setting the fan speed.

Press

to select the fan speed LOW, MED, HIGH, AUTO.

4. Setting the system mode

Press

to change the system mode HEATING, COOLING and

VENTILATION. In the mode of VENLITATION, the valve is off

but the fan runs.

5. Selecting manual, programming and Energy-saving

Mode

Press and hold

for 5 sec to switch between manual mode

and programming mode.

means manual mode.

means weekly programming mode.

Manual

Set Temp.

Fan Speed

Auto Fan

Net work

Energy Saving

Cooling

Ventilation

Heating

OWD

Programming

Week

Period

/Clock

Timing

ON/OFF

Mode

Fan