Inputs/outputs modules: MPNE
Mect Srl
21
ME7087_13 04/21
4
Modbus
4.1 Modbus parameters configurations
The 8th position dip-switch is used to change the baud rate, the address on the
MPNE1001 and the stop and parity bit.
Fig.: Modbus parameters configuration
4.1.1 Address (ID module)
The address is set using switches
3
to
8
, so the valid addresses are 1 to 63.
It is important that the address setting is carried out before the
MPNE1001 is
turned on because one of the first operations carried out at the turn-on is the
reading of the DIP status and if it detects that the
address is zero it
signals the
error condition: the LED LINK
flash.
The address is coded according to the following table:
S-3 S-4 S-5 S-6 S-7 S-8
ID node
0
0
0
0
0
0
Input in configuration
0
0
0
0
0
1
1
0
0
0
0
1
0
2
0
0
0
0
1
1
3
0
0
0
1
0
0
4
…
1
1
1
1
1
0
62
1
1
1
1
1
1
63
To set 1 on the DIP switch, the switch must be set to the ON side.
Fig.: Node address settings (ID)
Turn the device off and on again to make the changes effective.