Meco DIT 99 Скачать руководство пользователя страница 1

2

3

4

1

®

Digital Insulation Tester

Model : DIT 99

Instruction Manual

1. SPECIFICATIONS

1.1 General Specifications

DispIay

: 3½ digit liquid crystal display (LCD)

17mm height with a maximum reading
of 1999.

Overrange Indication

: (1) or (-1) is displayed at MSD

Low battery

: "       " is displayed when the battery

voltage drops below the operating
voltage.

Safety standard

: Meets the requirement of IEC 1010 for

insta1lation category II, 1000V phase to
earth.

Measurement rate

: 2.5 measurements per second nominal.

Operating conditions

: 0

0

C to + 50

0

C 0-75% RH

Storage conditions

: -20

0

C to + 60

0

C, 0-80% RH with battery

removed.

Accuracy

: Accuracy specifications at 23 ± 5

0

C,

less than 75% RH.

Power Supply

: 9 volts. 6 x 1.5V battery, Eveready

Dimensions

: 144.5(H) x 95(W) x 56.5(D) mm.

Weight

: 395 grams approx. including batteries

type 1015 or equivalent.

Accessories

: Test leads (pair) 6 X 1.5V battery,

instruction manual, carrying case.

Dielectric Strength

: 3.5kV @ 50Hz for 1 min. between Input

terminals and case

Insulation Resistance

: More than 50M

V

 at 500V between

circuit and case.

1.2 Electrical Specifications

Accuracies are ± (% reading plus number of digits at 23 ±
5

0

C, and humidity of less than 75% RH.

Model

DIT99A DIT99B DIT99C DIT99D DIT99E

Rated Voltage

100V

250V

500V

1000V

1000V

Range

20M

V

200M

V

200M

V

200M

V

2000M

V

Resolution

0.01M

V

0.1M

V

0.1M

V

0.1M

V

1M

V

Max. no load

+25% of rated voltage

voltage

Short circuit

<2mA

current
Accuracy

± (3%rdg + 2dgt)

2. SAFETY INFORMATlON

1. The circuit under test must be de energised and isolated before

connections ere made .

2. Circuit connections must not be touched during a test.
3. After Insulation tests capacitive circuits must be alIowed to be

discharged.

4. Test leads must be in good order, dean and have no cracked or

broken insuIation.

5. Do not push the test button before all connections and

preparations are done. The instrument must only be used by
suitably trained and competent persons.

Warning and safety symbols

Caution refer to this manual before using the meter.

Dangerous voltages.

Comply with lEC1010-1

3. OPERATION

Before taking any measurements, read the safety Information
section. Always examine the instrument for demage, contamination
(excessive dirt, grease, etc.) end defects Examine the teat leads for
cracked or frayed Insulation. If any abnormal conditions exist do not
make any measurements.

3.1 PRECAUTIONS

1. Disconnect aIl power from the circuit under test when making

measurements. If any voltage is present in the test circuit an
erroneous reading will result.

2. When the test switch la pressed a high voltage Is generated

between ‘+’ and ‘-’ terminals. Do not touch any live parts In the
circuit during measurement.