2
5
SAFETY &
EMC
(Note.5,7)
OTHERS
NOTE
SAFETY STANDARDS
I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:1.25KVAC
UL62368-1, CAN/CSA C22.2 No. 62368-1, TUV BS EN/EN62368-1, EAC TP TC 004 approved
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25
/ 70% RH
℃
281.2K hrs min.
Telcordia SR-332 (Bellcore) ; 28K hrs min. MIL-HDBK-217F (25
)
℃
SHP-10K: 460*211*83.5mm (L*W*H) SHP-10K-L: 460*216*83.5mm (L*W*H)
SHP-10K:
SHP-10K-L:
11.9Kg; 1pcs/11.9Kg/1.25CUFT
11.9Kg; 1pcs/11.9Kg/1.1CUFT
EN55024 , EN61204-3, EN61000-6-2
Parameter
Parameter
Standard
Standard
BS EN/EN55032 (CISPR32) / EN55011 (CISPR11)
BS EN/EN55032 (CISPR32) / EN55011 (CISPR11)
BS EN/EN61000-4-2
BS EN/EN61000-4-3
BS EN/EN61000-3-2
BS EN/EN61000-4-4
BS EN/EN61000-4-6
BS EN/EN61000-4-11
BS EN/EN61000-3-3
BS EN/EN61000-4-5
BS EN/EN61000-4-8
Test Level / Note
Test Level / Note
Class B
Level 3, 8KV air ; Level 2, 4KV contact
Class A
Level 3
Level 3
Level 3
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
-----
-----
Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
Level 4
Conducted
ESD
Radiated
Radiated
Harmonic Current
EFT / Burst
Conducted
Voltage Dips and Interruptions
Voltage Flicker
Surge
Magnetic Field
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
MTBF
DIMENSION
PACKING
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25
of ambient temperature.
℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance :includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltages. Please check the derating curve for more details.
5. Additional EMI filter is needed to meet regulations of EMC conducted and radiated emission. Characteristics of EMI filter please refer to the table,
Minimum Insertion Loss.
6. The efficiency is measured at 480VAC input.
7. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit
on
mm*
mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.
a
600
900
For guidance on
how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
8. The ambient temperature derating of 3.5
/1000m with fanless models and of 5
/1000m with fan models for operating altitude higher than 2000m
℃
℃
(6500ft).
9. If use PV signal to adjust Vo, under certain operations conditions, ripple noise of Vo might slightly go over rating defined in this specification.
0
1
.Under light load condition, output voltage ripple will exceed specification. The behavior can be minimized by increasing the load.
Product Liability Disclaimer
For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
※
:
EMC EMISSION
EMC IMMUNITY
6
2.4
erating curve
D
Blank
:
Type
AMBIENT TEMPERATURE ( )
℃
LO
A
D
(
%
)
-30
0
10
20
30
40
50
60
70
(HORIZONTAL)
20
40
50
60
80
100
2
L Type:
AMBIENT TEMPERATURE WITH WATER COOLING SYSTEM ( )
℃
LO
A
D
(
%
)
-30
0
10
20
30
40
50
60
70
(HORIZONTAL)
20
40
50
60
80
100