Installation Manual
Type
:
DUPS20/40 & DR-UPS40 DIN rail peripheral
DUPS20
DC INPUT
:
24-29V
20A
BATTERY IN/OUT
:
0
~
20A
DUPS40
DC INPUT
:
24-29V
40A
BATTERY IN/OUT
:
0
~
40A
DR-UPS40
DC INPUT
:
24-29V
40A
BATTERY IN/OUT
:
0
~
40A
Introduction
DUPS20/40 & DR-UPS40 are DIN rail periphera
ls
for
the UPS module.
Like other Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail.
Installation
(
1
)
Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating.
(
2
)
The appropriate mounting orientation for the unit is vertical, the TB1 terminals at the bottom. Mounting
orientations other than that, such as upside down, horizontal, or table-top mounting, is not allowed.
(
3
)
Use copper wire only, and recommended wires are shown as below.
AWG
18
16
14
12
10
8
6
Rated Current of
Equipment (Amp)
7A
10A
15A
20A
30A
40A
55A
Cross-section of
Lead(mm
2
)
0.8
1.3
2.1
3.3
5.3
8.4
13.3
Note: 1. Current each wire carries should be de-rated to 80% of the current suggested above when using
5 or more wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make sure
each contact is connected to wires to prevent too much current stress on a single contact.
(
4
)
Use wires that can withstand temperatures of at least 80°C, such as UL1007.
(
5
)
Recommended wire strapping length is 5mm (0.197”).
(
6
)
Recommended screwdriver is 4mm, slotted type.
(
7
)
The recommended torque setting for terminals is shown as below.
TB1
TB2
DUPS20
4kgf-cm (3.54Lb-in)
5.1kgf-cm (4.42Lb-in)
DUPS40
18kgf-cm (15.6Lb-in)
5.1kgf-cm (4.42Lb-in)
DR-UPS40
18kgf-cm (15.6Lb-in)
5.1kgf-cm (4.42Lb-in)