Installation Manual

 

 

 

 

Type

DRC series DIN rail peripheral

 

Series

DRC 40/60/100/180

 

DRC-40A    INPUT: 100-240VAC  0.8A  50/60Hz  OUTPUT: 13.8V    1.9A    BATTERY: 13.8V      1A 
DRC-40B    INPUT: 100-240VAC  0.8A  50/60Hz  OUTPUT: 27.6V    0.95A  BATTERY: 27.6V      0.5A 
DRC-60A    INPUT: 100-240VAC  1.3A  50/60Hz    OUTPUT: 13.8V    2.8A    BATTERY: 13.8V      1.5A 
DRC-60B    INPUT: 100-240VAC  1.3A  50/60Hz  OUTPUT: 27.6V    1.4A      BATTERY: 27.6V      0.75A 
DRC-100A   INPUT: 100-240VAC  1.8A  50/60Hz    OUTPUT: 13.8V    4.5A    BATTERY: 13.8V      2.5A 
DRC-100B   INPUT: 100-240VAC  1.8A  50/60Hz  OUTPUT: 27.6V    2.25A  BATTERY: 27.6V      1.25A 
DRC-180A   INPUT: 100-240VAC    2.5A  50/60Hz  OUTPUT: 13.8V    9A     BATTERY: 13.8V      4A 
DRC-180B   INPUT: 100-240VAC    2.5A    50/60Hz  OUTPUT: 27.6V    4.5A      BATTERY: 27.6V      2A 

   

 

Introduction 

DRC is a DIN rail type security power supply series

.

 

In addition to the primary output, there is a charger output with 

a smaller rated current, enabling the backup power supply application the security

 

access systems require. Like other 

Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail. 

 

 

Installation 

1

Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit 

in use to prevent it from overheating. 

2

The  appropriate  mounting orientation for the unit is vertical, the  TB1  terminals  at  the bottom. Mounting 

orientations other than that, such as upside down, horizontal, or table-top mounting, is not allowed. 

 
 
 
 
 
 

 

 

3

Use copper wire only, and recommended wires are shown as below 

AWG 

18 

16 

14 

12 

Rated Current of 

Equipment (Amp) 

7A 

10A 

15A 

20A 

Cross-section of 

Lead(mm

2

 ) 

0.8 

1.3 

2.1 

3.3 

Note: 1. Current each wire carries should be de-rated to 80% of the 

current suggested above when using 5 or more wires 

connected to the unit. 

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 

securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make sure 

each contact is connected to wires to prevent too much current stress on a single contact.   

4

Use wires that can withstand temperatures of at least 80°C, such as UL1007. 

5

Recommended wire strapping length is 5mm (0.197”). 

6

Recommended screwdriver is 4mm, slotted type. 

7

The recommended torque setting for terminals is shown as below. 

 