Installation Manual
Type
:
DRC series DIN rail peripheral
(
Series
:
DRC 40/60/100/180
)
DRC-40A INPUT: 100-240VAC 0.8A 50/60Hz OUTPUT: 13.8V 1.9A BATTERY: 13.8V 1A
DRC-40B INPUT: 100-240VAC 0.8A 50/60Hz OUTPUT: 27.6V 0.95A BATTERY: 27.6V 0.5A
DRC-60A INPUT: 100-240VAC 1.3A 50/60Hz OUTPUT: 13.8V 2.8A BATTERY: 13.8V 1.5A
DRC-60B INPUT: 100-240VAC 1.3A 50/60Hz OUTPUT: 27.6V 1.4A BATTERY: 27.6V 0.75A
DRC-100A INPUT: 100-240VAC 1.8A 50/60Hz OUTPUT: 13.8V 4.5A BATTERY: 13.8V 2.5A
DRC-100B INPUT: 100-240VAC 1.8A 50/60Hz OUTPUT: 27.6V 2.25A BATTERY: 27.6V 1.25A
DRC-180A INPUT: 100-240VAC 2.5A 50/60Hz OUTPUT: 13.8V 9A BATTERY: 13.8V 4A
DRC-180B INPUT: 100-240VAC 2.5A 50/60Hz OUTPUT: 27.6V 4.5A BATTERY: 27.6V 2A
Introduction
DRC is a DIN rail type security power supply series
.
In addition to the primary output, there is a charger output with
a smaller rated current, enabling the backup power supply application the security
access systems require. Like other
Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail.
Installation
(
1
)
Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating.
(
2
)
The appropriate mounting orientation for the unit is vertical, the TB1 terminals at the bottom. Mounting
orientations other than that, such as upside down, horizontal, or table-top mounting, is not allowed.
(
3
)
Use copper wire only, and recommended wires are shown as below
AWG
18
16
14
12
Rated Current of
Equipment (Amp)
7A
10A
15A
20A
Cross-section of
Lead(mm
2
)
0.8
1.3
2.1
3.3
Note: 1. Current each wire carries should be de-rated to 80% of the
current suggested above when using 5 or more wires
connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make sure
each contact is connected to wires to prevent too much current stress on a single contact.
(
4
)
Use wires that can withstand temperatures of at least 80°C, such as UL1007.
(
5
)
Recommended wire strapping length is 5mm (0.197”).
(
6
)
Recommended screwdriver is 4mm, slotted type.
(
7
)
The recommended torque setting for terminals is shown as below.