Installation Manual
Type
:
DRA DIN rail power supply
(
Series
:
DRA-40, DRA-60
)
DRA-40-12
INPUT: 100-240VAC 0.8A 50/60Hz
OUTPUT: 12V 3.34A
DRA-40-24
INPUT: 100-240VAC 0.8A 50/60Hz
OUTPUT: 24V 1.7A
DRA-60-12
INPUT: 100-240VAC 1.3A 50/60Hz
OUTPUT: 12V 5A
DRA-60-24
INPUT: 100-240VAC 1.3A 50/60Hz
OUTPUT: 24V 2.5A
Introduction
DRA is a DIN rail power supply series featuring adjustable output current. Users are able to set its output current to
a range of 10% - 100% of rated current via 1-10Vdc, PWM signal or resistance. Like other Mean Well’s DIN series,
they can be mounted on a TS35 Standard DIN rail.
Installation
(
1
)
Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a
heat source.
(
2
)
The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not
allowed.
(
3
)
Use copper wire only, and recommended wires are shown as below.
AWG
18
16
14
12
Rated Current of
Equipment (Amp)
7
10
15
20
Cross-section of
Lead(mm
2
)
0.8
1.3
2.1
3.3
Note
:
Current each wire carries should be de-rated to 80% of the current suggested
above when using 4-6 wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make
sure each contact is connected to wires to prevent too much current stress on a single contact.
(
4
)
Use wires that can withstand temperatures of at least 80°C, such as UL1007.
(
5
)
Recommended wire strapping length is 5mm (0.197”).
(
6
)
Recommended screwdriver is
3mm, slotted type.
(
7
)
The recommended torque setting for terminals(TB1) is 5 kgf‐cm (4.4 Lb‐in),
terminals(TB2) is 5.8 kgf‐cm (5 Lb‐in).
(
8
)
Each unit requires 0.15mA when dimming function is used. Please make sure your controller is capable of
driving the units.