Installation Manual

 

 

 

 

Type

DR Family with Class II

Series

DR-15, DR-30, DR-60, DR-100

 

DR-15-5 

INPUT: 100 -240VAC 0.88A 50/60Hz 

OUTPUT: 5V 2.4A 

DR-15-12 

INPUT: 100 -240VAC 0.88A 50/60Hz 

OUTPUT: 12V 1.25A 

DR-15-15 

INPUT: 100 -240VAC 0.88A 50/60Hz 

OUTPUT: 15V 1A 

DR-15-24 

INPUT: 100 -240VAC 0.88A 50/60Hz 

OUTPUT: 24V 0.63A 

DR-30-5 

INPUT: 100 -240VAC 1.1A 50/60Hz 

OUTPUT: 5V 3A 

DR-30-12 

INPUT: 100 -240VAC 1.1A 50/60Hz 

OUTPUT: 12V 2A   

DR-30-15 

INPUT: 100 -240VAC 1.1A 50/60Hz 

OUTPUT: 15V 2A 

DR-30-24 

INPUT: 100 -240VAC 1.1A 50/60Hz 

OUTPUT: 24V 1.5A 

DR-60-5 

INPUT: 100 -240VAC 1.8A 50/60Hz 

OUTPUT: 5V 6.5A 

DR-60-12 

INPUT: 100 -240VAC 1.8A 50/60Hz 

OUTPUT: 12V 4.5A 

DR-60-15 

INPUT: 100 -240VAC 1.8A 50/60Hz 

OUTPUT: 15V 4A 

DR-60-24 

INPUT: 100 -240VAC 1.8A 50/60Hz 

OUTPUT: 24V 2.5A 

DR-100-12  INPUT: 100 -240VAC 3A 50/60Hz   

OUTPUT: 12V 7.5A 

DR-100-15  INPUT: 100 -240VAC 3A 50/60Hz   

OUTPUT: 15V 6.5A 

DR-100-24  INPUT: 100 -240VAC 3A 50/60Hz   

OUTPUT: 24V 4.2A 

 

 

Introduction 

DR with class II is a double insulated DIN rail power supply series, meaning it is ungrounded. Like other Mean Well’s 
DIN series, they can be mounted on a TS35 Standard DIN rail. 

 

 

Installation 

1

Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit 

in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a 
heat source. 

2

The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on 

the  top  for  DR-15,  the  input  terminals  on  the  right  and  output  on  the  left  for  DR-30,  DR-60,  and  DR-100. 
Mounting  orientations  other  than  that,  such  as  upside  down,  horizontal,  or  table-top  mounting,  is  not 
allowed. 

 

 
 
 

 

3

Use stranded copper wire only, and recommended wires are shown as below. 

AWG 

18 

16 

14 

12 

Rated Current of 
Equipment (Amp) 

6A 

6-10A 

13-16A 

16-25A 

Cross-section of 
Lead(mm

2

 ) 

0.75 

1.00 

1.5 

2.5 

Note

Current each wire carries should be de-rated to 80% of the current suggested 

above when using 5 or more wires connected to the unit. 

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely  fixed  to  prevent  poor  contact.  If  the  power  supply  possesses  multi-output  terminals,  please  make 
sure each contact is connected to wires to prevent too much current stress on a single contact.   