13 Trouble shooting

 

Name 

Phenomenon 

Possible reasons

 

Solutions

   

Phase sequence 

failure 

The alarm signal output. 

a. Phase sequence failure. 

b. Lake phase.       

a.Exchange two wires of them.                               

b.Check whether the circuit is loose, 

please connect it again if yes. 

The pump 

overloading 

protection   

The power supply is normal, 

linkage and manual didn’t start 

pump.   

The pump overloading 

protection. 

After cut off power supply, replace the 

heating relay (press blue button), 

restart power supply.   

Passive interlock 

connect to the 

active interlock by 

mistake 

The pump didn

’t run. 

Linkage wire connecting is 

wrong. 

To make good connecting after 

confirm the linkage signal type. 

Contactor abnormal 

noise. 

Contactor makes abnormal 

noise after close. 

a. The contactor inside entered 

dirty or quality problem. 

b.The coil voltage is low. 

c. Bad contacting for circuit.         

a.Replace contactor. 

b.Check the voltage is normal or not. 

c.Wiring again to good connecting. 

The contactor is 

broken. 

Power supply and circuit are 

normal, 

can’t start it by linkage 

and manual, the coil voltage is 

normal. 

Cut off power supply, press on 

contactor by hand, the 

contactor is broken if don’t 

press down.   

Replace contactor. 

Relay failure. 

Normally start pump by 

manual, active start-up failure, 

corresponding light is not on. 

Relay failure. 

Replace relay. 

Water flow failure 

The air cooled scroll chiller has 

error signal output. 

a.The system lack water.   

b.The water flow switch 

selection wrong.   

c.Air in system.   

a.Check the replenishment pressure 

is normal or not. 

b.Reset the switch type of main unit 

flow or exchange flow switch. 

d.Exhaust enough. 

Pump with large 

noise   

The pump makes large noise 

in running. 

a.Pump reversal. 

b.Dirty in system or pump lock 

running. 

c.Return water pressure is low. 

d.Air in system. 

e.Return air inlet bad seal. 

a.Correctly adjudge the running 

direction of pump by pressure gauge 

and adjusting. 

b.Clean Y type filter,(The Y type filter 

must    be    installed, otherwise the 

dirty enter into pump so that the pump 

is broken, must be clean it after the 

first time running ) 

c.Check whether the replenishment 

water system is normal. 

d.Correctly install exhausting valve 

(make it on the top point of system), 

exhaust enough. 

e.Check whether the joint has smaller 

hole in pipeline, and fully seal. 

Содержание HM/II-130S

Страница 1: ...Application range 4 7 Specifications 4 8 Dimensions 5 9 Wiring Diagram 6 10 Exploded views 7 11 Selection 11 12 Key components configuration parameter 11 13 Trouble shooting 12 14 Installation 13 Manu...

Страница 2: ...e control cabinet can achieve linkage control with any formal air condition mainframe through active or passive junction 2 4 Easy installation and maintenance The unit can be installed indoor or outdo...

Страница 3: ...motor safety class is IP24 insulation class is F 3 External appearance 4 Nomenclature HM V II 65 S Power Supply S 380V 50Hz 3Ph D 220V 60Hz 3Ph Rated cooling capacity kW Water pump quantity I one pum...

Страница 4: ...25 Power supply frequency 2 Three phase current imbalance 5 7 Specifications Content Unit HM II 65S HM II 130S Recommended cooling capacity corresponding to the range selection kW 65 130 Water flow m...

Страница 5: ...MCAC ATSM 2014 11 Hydraulic Module 50Hz 5 8 Dimensions Unit mm HM II 65S HM II 130S...

Страница 6: ...Hydraulic Module 50Hz MCAC ATSM 2014 11 6 9 Wiring Diagram HM II 65S HM II 130S...

Страница 7: ...MCAC ATSM 2014 11 Hydraulic Module 50Hz 7 10 Exploded views HM II 65S...

Страница 8: ...0 1 Welded parts of electric control box 1 29 Water baffle II 1 10 2 Outdoor main control board ass y 1 30 Connection pipe of expansion tank 1 10 3 AC contactor 2 31 Right side board 1 10 4 Transforme...

Страница 9: ...MCAC ATSM 2014 11 Hydraulic Module 50Hz 9 HM II 130S...

Страница 10: ...ectric control box 1 29 Water baffle II 1 10 2 Outdoor main control board ass y 1 30 Connection pipe of expansion tank 1 10 3 AC contactor 2 31 Right side board 1 10 4 Transformer 1 32 Expansion tank...

Страница 11: ...oor unit combined quantity and type 3 Each water system design of pump head please refer to flow head curve 12 Key components configuration parameter No Name Connection dimension Parameter 1 Fixed pre...

Страница 12: ...t by linkage and manual the coil voltage is normal Cut off power supply press on contactor by hand the contactor is broken if don t press down Replace contactor Relay failure Normally start pump by ma...

Страница 13: ...e orifice and water pipe joint respectively in order to avoid the module set water pipe be damaged by large torque result in water pipe cracking and leakage 3 In order to improve the efficiency of wat...

Страница 14: ...it it must change the by pass valve of pressure difference to the position displays in the figure 5 If the module operates at lower temperature environment or don t use it for a long time please add e...

Страница 15: ...liding 4 Pipe installation Provide pipe installation schematic drawing and the name of connection orifice should be shown at the position of waterpower module orifice convenient to connect system pipe...

Страница 16: ...dismantled Lifting should be done as the packing direction and added two guard plates in case of damage or deformation 4 When suspension module to moving please use the flexible sling in order to avoi...

Страница 17: ...it nameplates is the quantitative value under standard running conditions The selection of miniature circuit breaker AC contactor wiring capacity and so on has been considered while the module is oper...

Страница 18: ...s pipeline 14 8 Safety in use 1 Should close down immediately dump checkup and repair if find following conditions A Electrical machine current exceed 10 or above of rated current for a long time B Ma...

Отзывы: