4.4.4.1 PI-control continuous
If the control value is selected as continuous PI control, the following setting options are available
(here: operating mode
“H
eating
”
):
Figure 26: Settings
–
PI control continuous
The following table shows the possible settings for continuous PI control:
ETS-Text
Dynamic range
[Default value]
Comment
Direction of controller
▪
normal
▪
inverted
Specifies the control behaviour
with rising temperature.
Maximum value of
control value
100%
; 90%; 80%; 75%; 70%; 60%;
50%; 40%; 30%; 25%; 20%; 10%; 0%
Specifies the output power of the
control value in maximum
operation.
Heating system
▪
Water heating (4K / 120 min)
▪
Underfloor heating (4K / 150 min)
▪
Split Unit (4K / 60min)
▪
Adjustment via control parameter
Setting of the heating system
used.
Individual parameterization
possible via setting 4.
Cooling system
▪
Split Unit (4K / 60 min)
▪
Cooling ceiling (4K / 150 min)
▪
Adjustment via control parameter
Setting of the cooling system
used.
Individual parameterization
possible via setting 3.
Proportional range
1 K - 20 K
[4 K]
Only visible with setting
"Adjustment via control
parameters
".
Here the proportional band can
be set freely.
Reset time
15 min
–
240 min
[150 min]
Only visible with setting
"Adjustment via control
parameters
".
The integral range can be freely
adjusted here.
Send control value
cyclically
not active, 1 min, 2 min, 3 min, 4 min,
5 min
, 10 min, 15 min, 20 min, 30 min,
40 min, 50 min, 60 min
Activation of cyclical sending of
the control value with setting of
the cycle time.
Table 62: Settings
–
PI control continuous