4.4 Temperature/Ventilation
4.4.1 Temperature measurement
The following picture shows the menu for temperature measurement:
Figure 10: Settings
–
Temperature measurement
The table shows the possible settings:
ETS-Text
Dynamic range
[Default value]
Comment
Temperature
measurement
▪
not active
▪
active
Activation/deactivation of the
temperature measurement.
Send measured value on
change of
…
not active
0,1 °C
–
5,0 °C
[0,2 °C]
Setting at which change the measured
value should be sent.
Send measured value
cyclically
not active
1
–
60 min
[20 min]
Cyclic sending of the measured value.
Sensor internal/external
▪
100% internal
▪
90% internal/ 10% external
▪
80% internal/ 20% external
▪
…
▪
100% external
Setting the weighting between internal
and external sensor.
Calibration value for
internal sensor
-
50 …
50 K x0,1 K
[0 K]
Adjustment for internal sensor.
Upper message value
not active
20
–
45 °C
Setting range of the upper/lower
message value.
Lower message value
not active
3
–
30 °C
Table 17: Settings
–
Temperature measurement