The following settings are available for all of the 6 channels. The associated communication objects
are valid for its channel.
4.2 Temperature measurement
The following settings are available at the ETS-Software:
Figure 5: Temperature measurement
The chart shows the dynamic range of the available parameters:
ETS-text
Dynamic range
[default value]
comment
Send actual value after change
of
(not available at SCN-RT6REG)
disable
0,1K - 2,0K
Sending condition for the actual
temperature value
Send actual temperature
cyclically
(not available at SCN-RT6REG)
disable
1 min
–
60 min
Activation of the cyclically sending of
the temperature value
Send min/max value
disable
Send enable
Activation of the sending of min/max
values
Internal sensor correction value
(value*0,1K)
(not available at SCN-RT6REG)
-50
–
50
[0]
Correction of the internal sensor
Internal/external sensor
(not available at SCN-RT6REG)
100% intern
90% intern/ 10% extern
80 % intern/ 20% extern
…
100% extern
Adjustment of the balance between
internal and external sensor
Table 4: Parameter Temperature measurement