Technical Manual – IP Router SCN-IP100.03
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
31
31
Telegram confirmations on
line
if routed
always
Defining whether the router should
send an Acknowledge
Send confirmation on own
telegrams
yes
no
Defining whether the router should
send an Acknowledge
Configuration from sub line
enable
disable
Defining whether it can be
programmed by TP side
Table 7: Settings – Sub line
If the "configure" parameter is active for the "Configuration", the following parameters are freely
adjustable.
For all other "Configuration" the parameters are set to fixed values - according to the setting.
The effects of the individual settings for the relevant parameters are described in detail below:
Group telegrams:
block
No group telegrams of the respective main groups are routed to KNX/EIB.
transmit all
All group telegrams of the respective main group are routed independently of the filter table
to KNX/EIB.
filter
Here is checked with the help of the filter table, whether the received group telegram will be
routed to KNX/EIB. The filter table is automatically generated by the ETS.
Configuration from sub line:
This parameter can be used to suppress programming from the TP/KNX side, thus achieving a higher
level of safety.