2 Byte shift of “Basic Comfort setpoint”
With the "2-byte shift of the Basic Comfort setpoint" the push-button sends a new basic comfort
setpoint to the controller to be activated. It evaluates the object "Status Basic Comfort setpoint" and
sends the new se/- the set step width to the controller to be actuated.
The range for the setpoint adjustment can be limited via the limits of the setpoint adjustment to be
set.
The following table shows the available communication objects:
Number Name/Object Function
Length Usage
0
F1/2:
–
Basic Comfort setpoint
2 Byte Sending the new, shifted setpoint.
1
F1/2:
–
Status actual temperature
2 Byte Receiving an external temperature for the display
of the current temperature - is only displayed if
the parameter "Use internal temperature value" is
set to "not active"
2
F1/2:
–
Status current setpoint
2 Byte Receiving the current setpoint temperature of the
temperature controller
–
to display the status
3
F1/2:
–
Status Basic Comfort setpoint
2 Byte Receipt of the Basic Comfort Setpoint. Must be
connected to the Basic Comfort Setpoint status of
the controller to be controlled in order to be able
to shift the Basic Comfort Setpoint correctly when
changing to another operating mode.
Table 49: Communication objects
–
2 Byte shift of Basic Comfort setpoint