Technical Manual
Glass Push Button II Smart & Push Button Smart 86
MDT technologies GmbH, Geschäftsbereich Gebäudeautomation
Phone: +49-2263-880
•
Fax: +49-2263-4588
•
E-Mail: [email protected]
•
www.mdt.de
49
49
The following table shows the available communication objects:
Number Name
Length
Usage
0
Push button 1:
Push buttons 1/2: –
Forcible control, percent value…
2 Bit
1 Byte
2 Byte
3 Byte
Sending the switching value.
DPT depending on the parameter setting
1
Push button 1:
Push buttons 1/2: –
State of percent value….
1 Byte
2 Byte
Receive the status for the display.
DPT depending on the parameter setting.
Status for forcible control, scene number
and RGB value not available
.
2
Push button 1 long:
Push buttons 1/2 long: – Switch
1 Bit
Switch function of long button.
Only appears if the setting "On or Off on
second object”
Table 35: Communication objects – Send Values - Subfunction: Switching values/scenes
4.4.5.3 Subfunction: Shift value
Two-button function
With the function "send values - shift values", values can be moved up or down within the set limits.
The following figure shows the available settings:
Figure 32: Settings – Send values - Subfunction: Shift values
The table below shows all available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Datapoint type
1 Byte (0...100%)
1 Byte (0…255)
Sets the datapoint type for the value
shift
Lower limit
0 – 100% / 0 – 255
[0%/0]
Sets the lower limit value for the
value shift
Upper limit
0 – 100% / 0 – 255
[100%/255]
Sets the upper limit value for the
value shift