4.7 Logic
The following figure shows the settings for the logic functions:
Figure 17: Settings - Logic
A total of 6 logic blocks are available, each of which can be assigned 4 input objects. These can be
evaluated both normally and inverted.
If the logic is fulfilled, the output object can send out a 1-bit value, a scene or a 1-byte value. In
addition, filter options and various transmission options are available for the 1-bit output object.
There are 3 different logical operations available:
▪
AND Function
▪
OR Function
▪
XOR Function
The parameter "Query logic objects after reset" applies to all 6 logic blocks and defines whether a
ReadRequest is sent for the input logics when the device is restarted.
The following table shows the available objects, here for logic A:
Number
Name
Length Usage
208
Input logic 1
1 Bit
Input object 1 of logic
209
Input logic 2
1 Bit
Input object 2 of logic
210
Input logic 3
1 Bit
Input object 3 of logic
211
Input logic 4
1 Bit
Input object 4 of logic
212
Output Switching/ Scene/ Value/
Percent value
1 Bit/
1 Byte
Output object of the logic. DPT
according to the setting
Table 27: Communication objects - Logic