The priority of the lock functions is as follows: Lock->Holidays->Public holidays.
4.10.4.3 Sperre/Freigabe
Für jede der 20 Funktionen kann eine Sperr-/Freigabefunktion aktiviert werden:
Figure 85: Time switch - Lock/Enabling
The following table shows all available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Lock/enabling
•
not active
•
locking object
•
enable object
Setting the type of lock object:
Lock object
= lock with 1, enable
with 0
Enable object
= enable with 1,
lock with 0
Action of the
Lock/enabling
•
no action
•
lock buttons
•
lock time switch
•
lock buttons and time
switch
Setting what the lock object
should lock
Behaviour during locking
•
no action
•
fix value (one time)
•
fix value (cyclic)
Setting of the behaviour to be
performed on
activation/duration of the lock
Value for lock
Adjustable value range
depends on the selected
function
Only visible if "Behaviour during
locking" is set to "Fixed value..".
The set value is sent when
locking.
Behaviour after bus power
return
•
nicht sperren
•
sperren
Setting the behaviour after bus
voltage recovery
Central lock of time switch
•
nicht aktiv
•
aktiv
Setting whether the central lock
is active for this function
Table 146: Settings: Time switch - Lock/Enabling