Technical Manual Switch Actuator 3-fold, FanCoil
MDT technologies GmbH
•
51766 Engelskirchen
•
Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.m
dt.de
58
The following table shows the available settings:
ETS-text
Dynamic range
[default value]
comment
Release time to automatic
mode
0-1440
[0]
Defines the time which starts after
switching into the direct mode. When
this time is elapsed, the FanCoil
switches back into the automatic mode.
Monitoring time of control
value
0-360min
[0 min]
Defines the time periods in which the
actuator must receive a valid control
value. If no control value is received, a
control value failure is released and the
FanCoil switches into the step for a
FanCoil failure..
Step at failure of control value
Off
Step 1
Step 2
Step 3
Step at a control value failure
Threshold for fan step 1
0-100%
[5%]
Defines from which value the FanCoil
switches into step 1.
Threshold for fan step 2
0-100%
[50%]
Defines from which value the FanCoil
switches into step 2.
Threshold for fan step 3
0-100%
[80%]
Defines from which value the FanCoil
switches into step 3.
Hysteresis
0-10%
[2%]
Defines the hysteresis for switching off
the current FanCoil step. Point of
switching off = Fan Step - Hysteresis
Dead time at switching
heating/cooling
0
–
1000s
[60s]
Defines the pause between
heating/cooling switchover. During this
dead time, the FanCoil is witched off
and both valves are closed.
Switchover between heating
and cooling
manually by object
automatically by control
value
Setting is only at 4-Pipe systems
available!
At the automatic switchover, the
heating mode is active when the control
value for heating has a value >0%. I the
control value for heating has a control
value =0% and the control value for
cooling has a control value >0%, the
cooling mode will be switched on. At
the automatic switchover, the object 5
–
Heating/Cooling Switchover works as
state object.
Table 50: Automatic mode - Control value
Содержание AKK-03UP.02