INSTALLATION

erant cooled oil coolers are provided and are com-
pletely piped up in the factory. Refrigerant cooling is

usually limited to the TP050  models.

Water Cooled Oil Coolers

When water is to be the coolant, the oil cooler is

factory mounted with the oil piping installed. Water

piping for the oil coolers must be installed in the field
according to good piping practice and should include:

stop valves to isolate the cooler for servicing, cleanable
strainer (40 mesh maximum), balancing valve to adjust
water flow, solenoid operated water shut-off valve
wired in accordance with Field Connection Control

Diagram, and a drain valve or plug. Water supply for

the oil cooler may be obtained from:

A. Source Water Circuit. See Figure 4.

B. Independent source, such as city water.

C. Cooling tower makeup if the flow is adequate and

continuous and the temperature never exceeds
90°F.  See Figure 5.

TABLE 1

Maximum Oil Cooler Water Requirements

And Pressure Drops

M a x i m u m   W a t e r

Water Requirement Pressure Drop Thru

M o d e l

 85 F Entering Oil Coolers Only

G P M   PSI

T E H 0 6 3   8.0 1.8

T E H 0 7 9   8.0 1.8

TEH100

12.25 5.2

T E H 1 2 6   16.0 10.4’

*Pressure drop through two oil coolers with water sides piped in

series - TEH 126 only.

When the oil cooler is piped into the source water
supply, its water piping should be connected across
the source water pump so that the full pressure
differential of the pump is maintained across the cooler
system at all times the pump is running. This is the

recommended arrangement, and most systems will
accommodate it. For those installations where it could
be desirable to pipe the oil cooler system across the
evaporator, this may be done providing the water
pressure drop through the evaporator is greater or
equal to the oil cooler pressure drop.

Under no circumstances should the oil cooler be piped
in parallel with a single pass evaporator. This will result
in inadequate cooling water to the oil cooler due to the
low evaporator pressure drop.

When supplied with city water, the oil cooler water

piping should discharge into an open drain to prevent

draining the cooler by siphoning. This water may also

be used for cooling tower makeup by discharging it
into the tower sump from a point above the highest
possible water level.

On R12 units, the water flow through the oil cooler

must be adjusted with the balancing valve so that the

temperature of oil supplied to the compressor bearings

(entering the compressor) is not less than 90°F nor
more than 120°F. On systems using source water for a
cooling medium, the leaving oil temperature should be
on the low side of the acceptable temperature range
when operating with the coldest water.

For R114  units oil temperatures are normally higher.
For settings consult special instructions furnished with

the unit.

FIGURE 5

OIL COOLER PIPING

On some units, oil cooler water solenoid valves are

factory furnished. On those units where the solenoid
valve is required and not furnished, the installing

contractor must supply the solenoid.

Refrigerant Cooled Oil Coolers

On those Templifier units furnished with refrigerant oil
cooling, the shut-off and flow control are built into the
refrigerant piping.

Subcooled liquid from the condenser is fed to the oil
cooler through an oil temperature control valve whose
control bulb is located on the oil line leaving the oil
cooler. The gas - liquid mixture returns to the inlet of

the evaporator. Refrigerant flow is controlled to main-

 

tain an oil temperature of approximately 

 in

R12 Templifiers. Oil Coolers in R114 Templiers operate

at higher temperatures.

6

Содержание Templifier

Страница 1: ...SINGLE AND DUAL COMPRESSOR CENTRIFUGAL TEMPLlFlER HEAT PUMPS 13600 Industrial Park Blvd P 0 Box 1551 Minneapolis Minnesota 55440...

Страница 2: ......

Страница 3: ...nameplate affixed with certain data for the installer including electrical data for the compressors and oil pumps MODEL STYLE SERIAL _ S O NO FACTORY CHARGED LBS REFRIGERANT _ LEAK TEST PRESSURE 100 P...

Страница 4: ...s to prevent damage to the control center and other components On units with side mounted compressors the unit can be lifted by the three corner fitting eyes and the extended eye at the compressor end...

Страница 5: ...AL OR FLANGE CONNECTIONS THE SOLID STATE TEMPERATURE SENSOR AND THERMOSTAT BULBS MUST BE REMOVED FROM THE WELLS TO PREVENT DAMAGE TO THOSE COMPONENTS Small water pressure test valves or pipe plugs are...

Страница 6: ...rop through the evaporator is greater or equal to the oil cooler pressure drop Under no circumstances should the oil cooler be piped in parallel with a single pass evaporator This will result in inade...

Страница 7: ...n practice for all installations NOTE Remove plastic thread protectors from the inside of the valves prior to making pipe connections Whenever vent piping is installed the lines should be run in accor...

Страница 8: ...an be determined by using GE No 546703265 phase sequence meter or equal Before connecting the starter load leads to the compressor terminals and while checking the field connection wiring the transiti...

Страница 9: ...ol center for proper connections The purpose of the water flow interlocks is to prevent compressor operation until both the source water and condenser water pumps are running and flow is proven 9 Oper...

Страница 10: ...OULD BE MAINTAINED ANY TIME REFRIGERANT IS ADDED OR REMOVED FROM THE SYSTEM CAUTION DO NOT USE OXYGEN TO BUILD UP PRESSURE AS A SERIOUS EXPLOSION CAN RESULT A pressure regulating valve should always b...

Страница 11: ...able and helpful in charging with that refrigerant Important At this point the charging procedure should be inter rupted and pre start checks made before attempting to complete refrigerant charge The...

Отзывы: