INSTALLATION

RECEIVING AND HANDLING

The unit should be inspected immediately after receipt
for possible shipping damage.

All McQuay Centrifugal Templifier Heat Pumps are
shipped F.O.B. factory and all claims for handling and
s h i p p i n g   d a m a g e   a r e   t h e   r e s p o n s i b i l i t y   o f   t h e

consignee.

Leave the shipping skid in place until the unit is in its

final position. This will aid in handling the equipment.

Extreme care should be used when rigging the equip-
ment to prevent damage to the control center, or
refrigerant piping.

On units with top mounted compressors, the unit can
be lifted by fastening the rigging hooks to the 4
corners of the evaporator where the rigging eyes are

located. (See Figure 2.) Spreader bars should be used

between the rigging lines to prevent damage to the
control center and other components.

On units with side mounted compressors, the unit can
be lifted by the three corner fitting eyes and the
extended eye at the compressor end. The center of
gravity is located approximately where the discharge
line enters the upper condenser shell. Adjust cable or
chain lenghs accordingly. The compressor support is
not designed to support the full weight of the unit.
Therefore, unit m u s t  be lifted so that it is level or
canted to assure that the compressor supports leave
the ground first and touch down last. Spreader

bars are a must. (See Figure 3).

For equipment weights for rigging and installation
requirements, refer to the certified equipment data.

FIGURE 3

SIDE MOUNTED COMPRESSOR UNITS

1. Lifting Eyes 5. Source Water - In

2. Shipping Skid 6. Source Water - Out
3. Condenser Water - In 7. Control Center
4. Condenser Water - Out 8. Condenser Relief Valves

FIGURE 7.

TOP MOUNTED COMPRESSOR UNITS

Содержание Templifier

Страница 1: ...SINGLE AND DUAL COMPRESSOR CENTRIFUGAL TEMPLlFlER HEAT PUMPS 13600 Industrial Park Blvd P 0 Box 1551 Minneapolis Minnesota 55440...

Страница 2: ......

Страница 3: ...nameplate affixed with certain data for the installer including electrical data for the compressors and oil pumps MODEL STYLE SERIAL _ S O NO FACTORY CHARGED LBS REFRIGERANT _ LEAK TEST PRESSURE 100 P...

Страница 4: ...s to prevent damage to the control center and other components On units with side mounted compressors the unit can be lifted by the three corner fitting eyes and the extended eye at the compressor end...

Страница 5: ...AL OR FLANGE CONNECTIONS THE SOLID STATE TEMPERATURE SENSOR AND THERMOSTAT BULBS MUST BE REMOVED FROM THE WELLS TO PREVENT DAMAGE TO THOSE COMPONENTS Small water pressure test valves or pipe plugs are...

Страница 6: ...rop through the evaporator is greater or equal to the oil cooler pressure drop Under no circumstances should the oil cooler be piped in parallel with a single pass evaporator This will result in inade...

Страница 7: ...n practice for all installations NOTE Remove plastic thread protectors from the inside of the valves prior to making pipe connections Whenever vent piping is installed the lines should be run in accor...

Страница 8: ...an be determined by using GE No 546703265 phase sequence meter or equal Before connecting the starter load leads to the compressor terminals and while checking the field connection wiring the transiti...

Страница 9: ...ol center for proper connections The purpose of the water flow interlocks is to prevent compressor operation until both the source water and condenser water pumps are running and flow is proven 9 Oper...

Страница 10: ...OULD BE MAINTAINED ANY TIME REFRIGERANT IS ADDED OR REMOVED FROM THE SYSTEM CAUTION DO NOT USE OXYGEN TO BUILD UP PRESSURE AS A SERIOUS EXPLOSION CAN RESULT A pressure regulating valve should always b...

Страница 11: ...able and helpful in charging with that refrigerant Important At this point the charging procedure should be inter rupted and pre start checks made before attempting to complete refrigerant charge The...