HOT GAS BYPASS (OPTIONAL)

Hot gas bypass is a system for maintaining evaporator pres-

sure at or above a minimum value. The purpose for doing
this is to keep the velocity of the refrigerant as it passes
through the evaporator high enough for proper oil return to
the compressor when cooling load conditions are light. Hot
gas bypass kits are described on page 9.

The solenoid valve should be wired to open whenever

the unit thermostat calls for the first stage of cooling (see

Figure 11). The pressure regulating valve that McQuay

offers is factory set to begin opening at 58 PSIG (32F for

R-22) 

when the air charged bulb is in an 8OF ambient

temperature. The bulb can be mounted anywhere as long as

it senses a fairly constant temperature at various load
conditions. The compressor suction line is one such
mounting location. It is generally in the 50F to 60F range.

The chart on page 50 indicates that when the bulb is
sensing 50F to 60F temperatures, the valve will begin
opening at 54 to 56 PSIG. This setting can be changed as

indicated above, by changing the pressure of the air charge
in the adjustable bulb. To raise the pressure setting, remove

the cap on the bulb and turn the adjustment screw clock-
wise. To lower the setting, turn the screw counterclockwise.

Do not force the adjustment beyond the range it is designed

for, as this will damage the adjustment assembly.

The regulating valve opening point can be determined by

slowly reducing the system load while observing the suction
pressure. When the bypass valve starts to open, the refrig-
erant line on the evaporator side of the valve will begin to
feel warm to the touch.

CAUTION: 

The hot gas line may become hot enough to

cause 

injury in a very short time so care should

be

 taken during valve checkout.

On installations where the condensing unit is remote

from the evaporator, it is recommended that the hot gas
bypass valve be mounted near the condensing unit to
minimize the amount of refrigerant that will condense in
the hot gas line during periods when hot gas bypass is not

required.

HOT GAS BYPASS PIPING DIAGRAM

HOT GAS BYPASS ADJUSTMENT RANGE

Hot Gas Bypass

Solenoid Valve

 

 Line

 

Inlet After

in ALP Unit

Bypass Valve Expansion Valve

(On DX Coils with
Distributors, use

Sporlan Auxiliary

 Connector

or Equivalent)

R E

M

OTE 

  A D J U S T

M

ENT RANGE

30

30

70

90 100

 

  A T   B U L B   L O C A T I O N

PAGE 42

Содержание SEASONCON ALP-037A

Страница 1: ...SEASONCON PACKAGED AIR COOLED CONDENSING UNIT MODELS ALP 037A THRU 057A 067B THRU 159B GROUP mcQua PEarEx Inc 13600 Industrial Park Blvd P O Box 1551 Minneapolis Mn 55440 c...

Страница 2: ......

Страница 3: ...hazard Avoid contact with them HANDLING Care should be taken to avoid rough handling or shock due to dropping the unit Do not push or pull the unit from anything other than the base and block the pus...

Страница 4: ......

Страница 5: ......

Страница 6: ...nt Risers A B are sized so that their combined cross sectional internal area will allow full load unit operation without excessive pressure drop see notes Table 4 Riser B is sized to provide adequate...

Страница 7: ...S McQuay has available a Liquid Line Accessory Kit for each ALP unit size Components selected for these kits were selected on the basis of a total combined pressure drop of 7 PSI includes 100 ft of tu...

Страница 8: ......

Страница 9: ...2 1 l 8 74 74 I I 159B 1 90 90 FIELD WIRING Wiring should be done in accordance with all applicable codes and ordinances Warranty is voided if wiring is not in accordance with specifications An open f...

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ...seal caps Making sure control stop switch Sl is open off and pumpdown switches PSI and PS2 are on manual pumpdown throw the main power and control dis connect switches to on This will energize crankc...

Страница 36: ...d compressor through the oil fill hole in the crankcase and to the Sundstrand compressor through the 3 8 inch process tube on the side of the compressor To add oil isolate the crankcase and pour or pu...

Страница 37: ...ning the refrigerant piping by moving pump down switches PSI and PS2 to the manual pumpdown valve assembly position The coil can then be removed from the valve body by simply removing a nut or snap ri...

Страница 38: ...s prepaid APPENDIX STANDARD CONTROLS NOTE PERFORM AN OPERATIONAL CHECK OF ALL UNIT SAFETY CONTROLS ONCE PER YEAR OIL PRESSURE SAFETY CONTROL The oil pressure safety control is a manually resettable de...

Страница 39: ...orator pressure will rise The highest evaporator pressure reached before compressor re start is the cut in setting of the control FANTROL HEAD PRESSURE CONTROL FANTROL is a method of head pressure con...

Страница 40: ...e to open or close the damper blades as required to maintain adequate condenser pressure The operators are factory set to begin opening the damper blades at 17Ozt 5 PSIG and to be fully open at 250 10...

Страница 41: ...ould pull in instantly NOTE Line is only hot when the unit thermostat calls for compressor to run COMPRESSOR LOCKOUT OPTIONAL ALP 037A THRU 078B Compressor lockout consists of a solid state time delay...

Страница 42: ...the pressure setting remove the cap on the bulb and turn the adjustment screw clock wise To lower the setting turn the screw counterclockwise Do not force the adjustment beyond the range it is designe...

Страница 43: ...drier 3 Replace cartrIdge Low Suction 4 Clogged suction line or compressor suction 4 Clean strainers Pressure gas strainers 5 Expansion valve malfunctioning 5 Check and reset for proper superheat 6 Co...

Отзывы: