LOW AMBIENT START (OPTIONAL)

Low ambient start 

is 

available on all units as an option with

FANTROL and included automatically with optional

SPEEDTROL or DAMPERTROL. It consists of a solid state

normally closed time delay wired in series with a relay.

These are both wired in parallel to the liquid line solenoid
valve so that when the solenoid valve is energized by the

unit thermostat, the low ambient start relay is also ener-

gized through the time delay. The relay has contacts that
essentially short-circuit the low pressure control and allow
the compressor to start with the low pressure control open.

After about 2-3/4 minutes, the time delay will open and

de-energize the r-clay. If the system has not built up enough
evaporator pressure to close the low pressure control, the
compressor will stop. The time delay can be reset to its
original normally closed position by moving the pumpdown

switch(es)  

  o r   P S 2   t o   t h e   “ m a n u a l   p u m p d o w n ”

position. Moving the pumpdown  switch back to the “auto.
pumpdown” position will again energize the relay for
another attempt at start-up. If the system has built up
enough evaporator pressure, the compressor will continue
to run.

To check the control, turn off all power to the unit and

remove the wire(s) leading to the terminals of the low pres-
sure control(s) LPI and LP2. Remove the compressor fuses
and jumper across terminals “L” and “M” of the freeze
control(s) and oil pressure safety control(s). Energize the
control circuit by turning on the control circuit disconnect
or main power disconnect (depending on the installation)
and the control stop switch 

Sl . 

The compressor contactors

should pull in instantly.

NOTE: 

Line is only hot when the unit thermostat calls for compressor to run.

COMPRESSOR LOCKOUT (OPTIONAL, ALP-037A THRU 078B)

Compressor lockout consists of a solid state time delay

wired in series with the compressor contactor( Its

purpose is to prevent rapid compressor cycling when
cooling demands are erratic. The circuit illustrated above is

for the lead compressor in each refrigerant circuit. T h e
circuit for the second compressor(s) performs the same
function but is wired differently (see unit wiring diagram).

When the unit thermostat no longer calls for cooling and

the compressor contactor have opened, the lockout time
delay breaks open the circuit preventing compressor

re-start.

The circuit remains open for a period of 5 minutes so

that, if the unit thermostat should call for cooling before
the delay period has expired, the compressor will not

restart. After 5 minutes, the time delay will close its

contacts to complete the circuit and be ready for start-up.
The time delay opens its contacts whenever power to
terminal 4 is interrupted and resets closed automatically
after the time delay period.

To check the control, the compressor(s) must be running

initially. Move the pumpdown  switch PSI or PS2 to the
“manual pumpdown” position. Immediately after the
compressor(s) have stopped running, move the pumpdown
switch back to the “auto pumpdown” position. The lead
compressor should not re-start for 5 minutes. The second
compressor in the refrigerant circuit should start approxi-

mately 20 seconds after the lead compressor, provided that

the cooling load is high enough to require it. Each refrig-
erant circuit can be checked the same way.

LINE

(SEE NO-I

 

 LOCKOUT

TIME DELAY

TO UNIT THERMOSTAT

N O T E :   Hot whenever freeze control and high

pressure control permit safe operation

PAGE 41

Содержание SEASONCON ALP-037A

Страница 1: ...SEASONCON PACKAGED AIR COOLED CONDENSING UNIT MODELS ALP 037A THRU 057A 067B THRU 159B GROUP mcQua PEarEx Inc 13600 Industrial Park Blvd P O Box 1551 Minneapolis Mn 55440 c...

Страница 2: ......

Страница 3: ...hazard Avoid contact with them HANDLING Care should be taken to avoid rough handling or shock due to dropping the unit Do not push or pull the unit from anything other than the base and block the pus...

Страница 4: ......

Страница 5: ......

Страница 6: ...nt Risers A B are sized so that their combined cross sectional internal area will allow full load unit operation without excessive pressure drop see notes Table 4 Riser B is sized to provide adequate...

Страница 7: ...S McQuay has available a Liquid Line Accessory Kit for each ALP unit size Components selected for these kits were selected on the basis of a total combined pressure drop of 7 PSI includes 100 ft of tu...

Страница 8: ......

Страница 9: ...2 1 l 8 74 74 I I 159B 1 90 90 FIELD WIRING Wiring should be done in accordance with all applicable codes and ordinances Warranty is voided if wiring is not in accordance with specifications An open f...

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ...seal caps Making sure control stop switch Sl is open off and pumpdown switches PSI and PS2 are on manual pumpdown throw the main power and control dis connect switches to on This will energize crankc...

Страница 36: ...d compressor through the oil fill hole in the crankcase and to the Sundstrand compressor through the 3 8 inch process tube on the side of the compressor To add oil isolate the crankcase and pour or pu...

Страница 37: ...ning the refrigerant piping by moving pump down switches PSI and PS2 to the manual pumpdown valve assembly position The coil can then be removed from the valve body by simply removing a nut or snap ri...

Страница 38: ...s prepaid APPENDIX STANDARD CONTROLS NOTE PERFORM AN OPERATIONAL CHECK OF ALL UNIT SAFETY CONTROLS ONCE PER YEAR OIL PRESSURE SAFETY CONTROL The oil pressure safety control is a manually resettable de...

Страница 39: ...orator pressure will rise The highest evaporator pressure reached before compressor re start is the cut in setting of the control FANTROL HEAD PRESSURE CONTROL FANTROL is a method of head pressure con...

Страница 40: ...e to open or close the damper blades as required to maintain adequate condenser pressure The operators are factory set to begin opening the damper blades at 17Ozt 5 PSIG and to be fully open at 250 10...

Страница 41: ...ould pull in instantly NOTE Line is only hot when the unit thermostat calls for compressor to run COMPRESSOR LOCKOUT OPTIONAL ALP 037A THRU 078B Compressor lockout consists of a solid state time delay...

Страница 42: ...the pressure setting remove the cap on the bulb and turn the adjustment screw clock wise To lower the setting turn the screw counterclockwise Do not force the adjustment beyond the range it is designe...

Страница 43: ...drier 3 Replace cartrIdge Low Suction 4 Clogged suction line or compressor suction 4 Clean strainers Pressure gas strainers 5 Expansion valve malfunctioning 5 Check and reset for proper superheat 6 Co...

Отзывы: