HIGH PRESSURE CONTROL

The high pressure control is a single pole pressure activated by watching condenser pressure rise. The highest point
switch that opens on a pressure rise to de-energize the reached before cut-out is the cut-out setting of the control.
entire control circuit except for compressor crankcase

heaters. It senses condenser pressure and is factory set to

open at 380 PSIG and can be manually reset closed at 315

PSIG. To check the control, either block off condenser

surface or start the unit with fuses in only one fan fuse

block (FBI 1) and observe the cut-out point of the control

CAUTION: 

Although there is an additional pressure relief

device in the system set at 450 PSIG,  it is
highly recommended that the 

 stop“

switch 

 be close at hand in case the high

pressure con trol should malfunction.

LOW PRESSURE CONTROL

The low pressure control is a single pole pressure switch
that closes on a pressure rise. It senses evaporator pressure
and is factory set to close at 60 PSIG and automatically
open at 25 PSIG. The control has an adjustable range of 20
inches of Hg. to 100 PSIG and an adjustable differential of
6 to 40 PSIG. To check the control (unit must be running),
move the pumpdown switch(es)  PSI and PS2 to the “man-
ual pumpdown” position. As the compressor pumps down,

condenser pressure will rise and evaporator pressure will
drop. The lowest evaporator pressure reached before cut-
out is the cutout setting of the control. By moving the
pumpdown switch(es)  PSI and PS2 to the “auto. pump-
down” position, evaporator pressure will rise. The highest
evaporator pressure reached before compressor re-start is
the cut-in setting of the control.

FANTROL -HEAD PRESSURE CONTROL

FANTROL is a method of head pressure control which

automatically cycles the condenser fans in response to con-

denser pressure and ambient air temperature. This main-
tains head pressure and allows the unit to run at low

and 14, circuit 1, and 23 and 24, circuit 2, are controlled
by ambient temperature and are factory set at the values
given in Table 13. Note that the number of fans on each
unit varies.

ambient air temperatures.

For ALP-037A thru 078B:

Models ALP-046A thru 078B have dual independent cir-
cuits with the fans for circuit 1 (11, 12, 13, 14) and circuit
2 (21, 22, 23, 24) being controlled independently by the
condensing pressure and ambient air of each circuit. Fans

11 and 21 start with each compressor and fans 12 and 22

cycle on and off in response to condenser pressure. The
cut-out and cut-in pressures are given in Table 13. Fans 13

TABLE 13. FACTORY FANTROL SETTINGS

For ALP-089B thru 159B:

The first fan (1 1) is started when the first compressor in the
unit starts. Fan 12 is controlled by parallel wired pressure
switches which sense condenser pressure in circuit 1 and 2.
The third fan (13) is controlled by parallel wired tempera-
ture switches, one of which senses condenser inlet air for
circuit 1 and the other senses condenser inlet air for circuit
2. Refer to Table 13 for cut-out and cut-in settings of these
controls.

ALP-067B 270 PSI 170 PSI 270 PSI 170 PSI 74F 69F 7 4 F   6 9 F   6 9 F   6 4 F   6 9 F   64F

A L P - 0 7 8 6   280 PSI 170 PSI 280 PSI 170 PSI 74F 6 9 F   74F 6 9 F   6 6 F   61F 66F 61 F

ALP-089B

T H R U

2 7 0   170

_

8 0 F t

_

_ _

ALP-159B

 

 PC2

 and TC6

PAGE 39

Содержание SEASONCON ALP-037A

Страница 1: ...SEASONCON PACKAGED AIR COOLED CONDENSING UNIT MODELS ALP 037A THRU 057A 067B THRU 159B GROUP mcQua PEarEx Inc 13600 Industrial Park Blvd P O Box 1551 Minneapolis Mn 55440 c...

Страница 2: ......

Страница 3: ...hazard Avoid contact with them HANDLING Care should be taken to avoid rough handling or shock due to dropping the unit Do not push or pull the unit from anything other than the base and block the pus...

Страница 4: ......

Страница 5: ......

Страница 6: ...nt Risers A B are sized so that their combined cross sectional internal area will allow full load unit operation without excessive pressure drop see notes Table 4 Riser B is sized to provide adequate...

Страница 7: ...S McQuay has available a Liquid Line Accessory Kit for each ALP unit size Components selected for these kits were selected on the basis of a total combined pressure drop of 7 PSI includes 100 ft of tu...

Страница 8: ......

Страница 9: ...2 1 l 8 74 74 I I 159B 1 90 90 FIELD WIRING Wiring should be done in accordance with all applicable codes and ordinances Warranty is voided if wiring is not in accordance with specifications An open f...

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ...seal caps Making sure control stop switch Sl is open off and pumpdown switches PSI and PS2 are on manual pumpdown throw the main power and control dis connect switches to on This will energize crankc...

Страница 36: ...d compressor through the oil fill hole in the crankcase and to the Sundstrand compressor through the 3 8 inch process tube on the side of the compressor To add oil isolate the crankcase and pour or pu...

Страница 37: ...ning the refrigerant piping by moving pump down switches PSI and PS2 to the manual pumpdown valve assembly position The coil can then be removed from the valve body by simply removing a nut or snap ri...

Страница 38: ...s prepaid APPENDIX STANDARD CONTROLS NOTE PERFORM AN OPERATIONAL CHECK OF ALL UNIT SAFETY CONTROLS ONCE PER YEAR OIL PRESSURE SAFETY CONTROL The oil pressure safety control is a manually resettable de...

Страница 39: ...orator pressure will rise The highest evaporator pressure reached before compressor re start is the cut in setting of the control FANTROL HEAD PRESSURE CONTROL FANTROL is a method of head pressure con...

Страница 40: ...e to open or close the damper blades as required to maintain adequate condenser pressure The operators are factory set to begin opening the damper blades at 17Ozt 5 PSIG and to be fully open at 250 10...

Страница 41: ...ould pull in instantly NOTE Line is only hot when the unit thermostat calls for compressor to run COMPRESSOR LOCKOUT OPTIONAL ALP 037A THRU 078B Compressor lockout consists of a solid state time delay...

Страница 42: ...the pressure setting remove the cap on the bulb and turn the adjustment screw clock wise To lower the setting turn the screw counterclockwise Do not force the adjustment beyond the range it is designe...

Страница 43: ...drier 3 Replace cartrIdge Low Suction 4 Clogged suction line or compressor suction 4 Clean strainers Pressure gas strainers 5 Expansion valve malfunctioning 5 Check and reset for proper superheat 6 Co...

Отзывы: