SERVICE

NOTE: Service on this equipment is to be performed by qualified refrigeration service personnel. Causes for repeated tripping
of safety controls must be investigated and corrected. CAUTION: Disconnect all power before doing any service inside the
unit.

FILTER-DRIERS

To change the filter-drier core(s), pump the unit down by

moving pumpdown switches PSI and PS2 to the “manual
pumpdown” position. Turn off all power to the unit and
install jumpers across the terminals shown in the table.

UNIT SIZE

JUMPER ACROSS

CIRCUIT NO.

T E R M I N A L S

 THRU 

1 114 to 116

ALP-046A T H R U

2 214 to 2 1 6

ALP-089A TH RU

1 1 1 4 t o 118

T H R U 159A 2 214 

to

2 1 8

Turn power to the unit back on and restart the unit by

moving pumpdown switches PSI and PS2 to the “auto.
pumpdown” position. Close the manual liquid line shut-off
valve(s) and when evaporator pressure reaches 0 PSIG,
move the control stop switch 

 to the “off” position. This

will close the liquid line solenoid valve(s) and isolate the
short section of refrigerant piping containing the filter-
drier(s). Remove the cover plate from the filter-drier shell

and replace the core(s).

After core replacement, replace the cover plate. A leak

check around the flange of the filter-drier shell is recom-
mended after the cores have been changed.

LIQUID LINE SOLENOID VALVE

The liquid line solenoid valves, which are responsible for
automatic pumpdown during normal unit operation, do not

normally require any maintenance. They may, however,

require replacement of the solenoid coil or of the entire

The solenoid coil may be removed from the valve body

without opening the refrigerant piping by moving pump-
down switches PSI and PS2 to the “manual pumpdown”

valve assembly.

position. The coil can then be removed from the valve body

by simply removing a nut or snap-ring located at the top of
the coil. The coil can then be slipped off its mounting stud

To replace the entire solenoid valve, the unit must be

for replacement. Be sure to replace the coil on its mounting

pumped down by use of the manual liquid line shut-off

stud before returning pumpdown switches PSI and PS2 to

valve.

the “auto. pumpdown” position.

THERMOSTATIC EXPANSION VALVE

The expansion valve is responsible for allowing the proper
amount of refrigerant to enter the evaporator regardless of
cooling load. It does this by maintaining a constant super-

heat. (Superheat is the difference between refrigerant
temperature as it leaves the evaporator and the saturation

temperature corresponding to the evaporator pressure.)
Typically, superheat should run in the range of 

 to 15F.

On valves purchased through McQuay,  the superheat setting
can be adjusted by removing a cap at the bottom of the
valve to expose the adjustment screw. Turn the screw clock-
wise (when viewed from the adjustment screw end) to

I N L E T

increase the superheat setting and counterclockwise to
reduce superheat. Allow time for system rebalance after

each superheat adjustment.

The expansion valve, like the solenoid valve, should not

normally require replacement, but if it does, the unit must
be pumped down by using the manual liquid line shut-off
valve. If this problem can be traced to the power element

only, it can be unscrewed from the valve body without

removing the valve, but only after pumping the unit down
with the manual liquid  line shut-off valves.

 POWER ELEMENT

(CONTAINS DIAPHRAGM)

O U T L E T

 

. -   S P R I N G

 S

C R E W

PAGE 37

Содержание SEASONCON ALP-037A

Страница 1: ...SEASONCON PACKAGED AIR COOLED CONDENSING UNIT MODELS ALP 037A THRU 057A 067B THRU 159B GROUP mcQua PEarEx Inc 13600 Industrial Park Blvd P O Box 1551 Minneapolis Mn 55440 c...

Страница 2: ......

Страница 3: ...hazard Avoid contact with them HANDLING Care should be taken to avoid rough handling or shock due to dropping the unit Do not push or pull the unit from anything other than the base and block the pus...

Страница 4: ......

Страница 5: ......

Страница 6: ...nt Risers A B are sized so that their combined cross sectional internal area will allow full load unit operation without excessive pressure drop see notes Table 4 Riser B is sized to provide adequate...

Страница 7: ...S McQuay has available a Liquid Line Accessory Kit for each ALP unit size Components selected for these kits were selected on the basis of a total combined pressure drop of 7 PSI includes 100 ft of tu...

Страница 8: ......

Страница 9: ...2 1 l 8 74 74 I I 159B 1 90 90 FIELD WIRING Wiring should be done in accordance with all applicable codes and ordinances Warranty is voided if wiring is not in accordance with specifications An open f...

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ......

Страница 33: ......

Страница 34: ......

Страница 35: ...seal caps Making sure control stop switch Sl is open off and pumpdown switches PSI and PS2 are on manual pumpdown throw the main power and control dis connect switches to on This will energize crankc...

Страница 36: ...d compressor through the oil fill hole in the crankcase and to the Sundstrand compressor through the 3 8 inch process tube on the side of the compressor To add oil isolate the crankcase and pour or pu...

Страница 37: ...ning the refrigerant piping by moving pump down switches PSI and PS2 to the manual pumpdown valve assembly position The coil can then be removed from the valve body by simply removing a nut or snap ri...

Страница 38: ...s prepaid APPENDIX STANDARD CONTROLS NOTE PERFORM AN OPERATIONAL CHECK OF ALL UNIT SAFETY CONTROLS ONCE PER YEAR OIL PRESSURE SAFETY CONTROL The oil pressure safety control is a manually resettable de...

Страница 39: ...orator pressure will rise The highest evaporator pressure reached before compressor re start is the cut in setting of the control FANTROL HEAD PRESSURE CONTROL FANTROL is a method of head pressure con...

Страница 40: ...e to open or close the damper blades as required to maintain adequate condenser pressure The operators are factory set to begin opening the damper blades at 17Ozt 5 PSIG and to be fully open at 250 10...

Страница 41: ...ould pull in instantly NOTE Line is only hot when the unit thermostat calls for compressor to run COMPRESSOR LOCKOUT OPTIONAL ALP 037A THRU 078B Compressor lockout consists of a solid state time delay...

Страница 42: ...the pressure setting remove the cap on the bulb and turn the adjustment screw clock wise To lower the setting turn the screw counterclockwise Do not force the adjustment beyond the range it is designe...

Страница 43: ...drier 3 Replace cartrIdge Low Suction 4 Clogged suction line or compressor suction 4 Clean strainers Pressure gas strainers 5 Expansion valve malfunctioning 5 Check and reset for proper superheat 6 Co...

Отзывы: