IOMM Starter
59
Fault/Log Codes
The following is a list of the possible fault and log codes that can be generated depending on
the type of starter.
The fault class lists the default setting for each fault; either critical or non-critical.
NonC = Non-critical
Crit = Critical
Table 20, Fault/Log Codes
Fault/
Log No.
Fault
Class
Fault/Event
Recorder Text
Description/Possible Solutions
1
NonC
Sequence Not CBA
Incoming phase sequence is actually ABC but starter is set to CBA
2
NonC
Sequence Not ABC
Incoming phase Sequence is actually CBA but starter is set to ABC
3
NonC
No Phase Order
No phase order detected.
4
NonC
High Freq. Trip
Line frequency went above the high freq. trip setting
Line power quality problem.
Low control power problem.
Generator governor is malfunctioning
5
NonC
Low Freq. Trip
Line frequency went below the low freq. trip setting
Line power quality problem.
Low control power problem.
Generator governor malfunctioning.
6
NonC
Jog Not Allowed
Jog input (JC13-4) was energized while the starter was running.
Stop the starter by removing the run command before requesting a jog
(JC13-4).
7
NonC
100% Not Allowed
The jog input (JC13-4) was de-energized while the starter was operating
in the jog mode.
Stop the starter by removing the run command before removing the
(JC13-4).
9
NonC
Dir Change Fault
The jog direction was changed while the starter was operating in the jog
mode.
Stop the starter by removing the run command before changing the
reversing input (JC13-6).
15
Crit
Phase Order Err
Phase order error.
16
Crit
Bad OP Code Err
Bad operating-code error
17
NonC
Over voltage L1
The voltage on line 1 went above the high/low voltage setting
18
NonC
Over voltage L2
The voltage on line 2 went above the high/low voltage setting
19
NonC
Over voltage L3
The voltage on line 3 went above the high/low voltage setting
20
NonC
Low line voltage#1
The voltage on line 1 went below the high/low voltage setting
21
NonC
Low line voltage#2
The voltage on line 2 went below the high/low voltage setting
22
NonC
Low line voltage#2
The voltage on line 3 went below the high/low voltage setting
23
NonC
Curr. Imbal. HL1
The current on line 1 went above the current imbalance setting
24
NonC
Curr. Imbal. HL2
The current on line 2 went above the current imbalance setting
25
NonC
Curr. Imbal. HL3
The current on line 3 went above the current imbalance setting
26
NonC
Curr. Imbal. LL1
The current on line 1 went below the current imbalance setting
27
NonC
Curr. Imbal. LL2
The current on line 2 went below the current imbalance setting
28
NonC
Curr. Imbal. LL3
The current on line 3 went below the current imbalance setting
29
Crit
Bad RAM Battery
Bad RAM battery.
Replace IC16 or computer card to correct problem.
To clear fault, hold the down arrow key and perform a computer reset. Co
the down arrow key until fault 30 appears on the display
30
Crit
Def Param Loaded
The factory defaults for the parameters have been loaded.
Reset the computer to clear the fault.
All parameters have to be re-programmed as necessary.
31
NonC
REV Not Allowed
Starter is not a reversing unit.
Remove reverse command from reverse input (JC13-6).
46
NonC
BIST Canceled
The Built-in Self Test was canceled.
The disconnect was closed.
Line power was applied to the starter.
49
NonC
Tach Loss
There was no tachometer feedback signal detected when a start was com
Continued on next page.
Содержание RVSS14