Starter
Table 19, Other situations.
Display
Cause
Solution
Power Metering not working.
CT installed wrong.
Fix CT installation. White dot to line side.
TruTorque Ramp not working.
CT installed wrong.
Fix CT installation. White dot to line side
Motor current or voltage fluctuat
load.
Motor
Energy saver
Power connection.
Verify motor is operating correctly.
Set energy saver to off.
Shut off power and check connections
Erratic operation.
Loose connections.
Shut off all power and check connections.
Accelerates too quickly.
Ramp time.
Initial current.
Maximum current setting.
Kick Start.
Improper FLA setting.
Initial torque.
Maximum torque.
Contact McQuay Factory Service
Accelerates too slowly
Ramp time.
Initial current.
Maximum current setting.
Kick Start.
Improper FLA setting.
Initial torque.
Maximum torque.
Contact McQuay Factory Service
Motor overheats.
Duty cycle.
High ambient.
Too long acceleration time.
Wrong overload setting.
Too long jog cycle.
Cool between starts.
Provide better ventilation.
Reduce motor load.
Select correct overload setting.
Jog operation reduces motor cooling
current. Shorten jog cycle.
Motor short circuit.
Wiring fault.
Power factor correction capacitors (P
starter output.
Identify fault and correct.
Move PFCC to line side of starter.
Fans do not operate
Wiring.
Fuse.
Fan failed.
Check wiring and correct.
Replace fuse.
Replace fan.
Display buttons don’t work.
Display ribbon cable.
Display faulty.
Check cable on back of display.
Replace display.