IOMM Starter
41
Code
Description
Detailed Description of Fault / Possible Solutions
Line frequency above 72 Hz was detected.
Verify input line frequency.
If operating on a generator, check generator speed governor for malfunctions.
F13
High Line
Frequency
Line power quality problem / excessive line distortion.
Three-phase power has been detected when the starter is expecting single-phase power.
Verify that input power is single phase.
Verify that single-phase power is connected to the L1 and L2 inputs. Correct wiring if
necessary.
F14
Input power
not single
phase
Verify that the SCR gate wires are properly connected to the D3 control board.
Single-phase power has been detected when the starter is expecting three-phase power.
Verify that input power is three phase. Correct wiring if necessary.
Verify that the SCR gate wires are properly connected to the D3 control board.
F15
Input power
not three
phase
On medium voltage systems, verify wiring of the voltage feedback measurement circuit.
Low voltage below the Undervoltage Trip Level parameter setting (PFN 08, P31) was
detected for longer than the Over/Under Voltage Trip delay time (PFN 09, P32).
Verify that the actual input voltage level is correct.
Verify that the Rated Voltage parameter (FUN 05,
P66
) is set correctly.
Check input supply for open fuses or open connections.
F21
Low Line L1-
L2
On medium voltage systems, verify wiring of the voltage measurement circuit.
Low voltage below the Undervoltage Trip Level parameter setting (PFN 08, P31) was
detected for longer than the Over/Under Voltage Trip delay time (PFN 09, P32).
Verify that the actual input voltage level is correct.
Verify that the Rated Voltage parameter (FUN 05,
P66
) is set correctly.
Check input supply for open fuses or open connections.
F22
Low Line L2-
L3
On medium voltage systems, verify wiring of the voltage feedback measurement circuit.
Low voltage below the Undervoltage Trip Level parameter setting (PFN 08, P31) was
detected for longer than the Over/Under Voltage Trip delay time (PFN 09, P32).
Verify that the actual input voltage level is correct.
Verify that the Rated Voltage parameter (FUN 05,
P66
) is set correctly.
Check input supply for open fuses or open connections.
F23
Low Line L3-
L1
On medium voltage systems, verify wiring of the voltage feedback measurement circuit.