IOMM Starter
23
DESCRIPTION
Values
DEFAULT
P6
Sequence Complete
Delay Time
0.1 to 5.0 seconds
2.0
P7
Overcurrent Trip Level
OFF, 50 to 800 %RLA
OFF
P8
Overcurrent Trip Delay
Time
0.1 to 90.0 seconds
2.0
P9
Rated RMS Voltage
100, 110, 120, 200, 208,
220, 230, 240, 350, 380,
400, 415, 440, 460, 480,
575, 600, 660, 1000 Volts
480
P10
Over Voltage Trip Level
OFF, 1 to 40 % rated Volts
10
P11
Under Voltage Trip Level
OFF, 1 to 40 % rated Volts
15
P12
Over/Under Voltage
Delay Time
0.1 to 90.0 seconds
1.0
P13
Current Imbalance Trip
Level
5 to 40 %
20
P14
Auto Fault Reset Time
OFF, 1 to 120 seconds
60
P15 CT
Ratio
72, 96, 144, 288, 864,
2640, 2880, 5760, 8000
2640
P16 Control
Source
TEr: Terminal
NEt: Network
tEr
P17
Modbus Address
1 to 247
2
P18
Modbus Baud Rate
1.2, 2.4, 4.8, 9.6, 19.2 Kbps
19.2
P19
Modbus Timeout
OFF, 1 to 120 seconds
3
P20
Analog Output Function
0 to 11
1
P21
Analog Output Span
1 to 125 %
100
P22
Analog Output Offset
0 to 99 %
0
P23
Passcode
0 to 9999
–
P24 Fault
Log
x
F
yy
–
Fault/Alarm Codes (LVYD)
Description
Auto
Reset
00
No fault
-
02
Motor Thermal Overload Trip
N
10
Phase Rotation Error, not ABC
Y
12
Low Line Frequency
Y
13
High Line Frequency
Y
15
Input power not three phase
Y
21
Low Line L1-L2 Voltage
Y
22
Low Line L2-L3 Voltage
Y
23
Low Line L3-L1 Voltage
Y
24
High Line L1-L2 Voltage
Y
25
High Line L2-L3 Voltage
Y
26
High Line L3-L1 Voltage
Y
27 Phase
Loss
Y
28 No
Line
Voltage
Y
30
I.O.C. (Instantaneous Overcurrent)
N
31 Overcurrent
N
37 Current
Imbalance
Y
38 Ground
Fault
N
39
No Current at Run
Y
40
Open Line or Motor Lead
N
41 Current
While
Stopped
N
48
2M Feedback Fault (on DIN#2)
N
50
Control Power Low
Y
51
Current Sensor Offset Error
N
Содержание RVSS14