IOMM Starter
19
Emergency Thermal Reset·
•
Press RESET and DOWN to perform an emergency thermal reset.
Messages (LVSS)
No Line
Ready
Accelerating
Up to Speed
Run – Done with ramp but not yet
Up to Speed.
Decelerating
Overload Alarm – The motor
overload level is between 90% and
100%.
Overload Fault – The motor
overload level has reached 100%.
Overload Lockout – A start is not
allowed until the motor overload
level cools below 60%.
Control Power Lockout – A start is
not allowed because the control
power is too low.
xxx xxx = overload content. Press
DOWN
to toggle.
xx xx = Alarm code. If the condition
persists, a fault will occur.
xx xx = Fault code. Press
RESET
to
clear.
Instantaneous Overcurrent – Press
RESET
to clear.
Default – Flashes when parameter
defaults are loaded.
Default Meter Display (P13) (LVSS)
0: Status
1:
Ave RMS Current
2:
L1 RMS Current
3:
L2 RMS Current
4:
L3 RMS Current
5:
Current Imbalance %
6:
Ground Fault Current
7:
Ave L-L Voltage RMS
8:
L1-L2 Voltage RMS
9:
L2-L3 Voltage RMS
10: L3-L1 Voltage RMS
11: Overload
%
12: PF
13: KW
14: KVA
15: KWh
16: MWh
17: Phase
Rotation
18: Line
Frequency
19: Analog
Input
Analog Output Function (P28) (LVSS)
0:
OFF (no output)
1:
Ave Current (0 – 200% RLA)
2:
Ave Current (0 – 800% RLA)
3:
Ave Voltage (0 – 750VAC)
4: Thermal
Overload%
5:
KW (0 - 10KW)
6:
KW (0 – 100KW)
7:
KW (0 – 1MW)
8:
KW (0 – 10MW)
9: Analog
Input
10: Output Voltage (% of FV)
11: Calibrate (full 100% output)
CT Burden Switch Settings (P1 and P23) (LVSS)
FLA in Amps
Setting
864:1 CTs
2640:1 CTs
5760:1 CTs
8000:1 CTs
SW1
SW2
24 to 42
73 to128
160 to 280
223 to 390
Off
Off
42 to 50
128 to 151
280 to 330
390 to 465
Off
On
50 to 108
151 to 330
330 to 720
465 to 1000
On
Off
108 to 190
330 to 590
720 to 1280
1000 to 1800
On
On
Parameters (LVSS)
DESCRIPTION
Values
DEFAULT
SET
TO:
P1
Motor FLA
1 to 9999 Amps
10
P2
Motor RLA
1 to 9999 Amps
10
P3
Motor Service Factor
1.00 to 1.99
1.08
P4
Motor Overload Class
OFF, 1 to 40
10
P5
Initial Motor Current
50 to 400 %FLA
250
P6
Maximum Motor Current
100 to 800 %FLA
300
P7
Ramp Time
0 to 300 seconds
10
P8
UTS Time
1 to 900 seconds
15
P9 Stop
Mode
CoS: Coast
dcL: Voltage Decel
CoS
P10
Decel Begin Level
100 to 0 %Volts
40
Continued on next page.