background image

IM 1014 / Page 1 of 2

© 2009 McQuay International

800-432-1342

 www.mcquay.com

Installation

1

Install the thermostat with the two furnished mounting 

screws to a standard 2" x 4" electrical box, 4-11/16" x 2-
1/8" square device box with a 2" x 4" adapter ring or to a 
4" x 4" box with accessory adapter plate.

2

For wall installations, mount the thermostat on an inside 
wall approximately 5 feet above the floor. The location 
should provide circulation at average room temperature. 
Avoid direct sunlight or sources of hot or cold air in the 
room or wall.

3

Remove the knob and then the cover. Mount thermostat 
base assembly to the outlet box using the screws 
provided, tighten the screws evenly but do not over 
tighten. Make wiring connections as noted.

4

To use a remote sensor, remove jumper JP-1 to disable 
local sensing. See 

Figure 1

. Failure to remove JP-1 when 

using a remote sensor will cause improper operation of 
the thermostat. Some units do not have remote sensing 
capability. See 

Application Notes

.

Figure 1: Removing Jumper JP-1 

5

Reinstall the cover assembly. Install cover locking screw 
provided. Reinstall the knob.

6

Checkout: After wiring and installation are complete, 
energize the system and check the operation. Adjust the 
thermostat as necessary to complete at least one cycle. 
Be sure the thermostat and all other equipment are 
functioning correctly.

Thermostat Operation

Temperature Range: 50°F - 90°F (10°C - 32°C)

TA155: A HEAT-OFF-COOL system switch manually selects 
heating or cooling mode. In the HEAT position, only the heat 
output cycles with demand. In the COOL position, only the 
cool output cycles with demand. In the OFF position, heating 
and cooling outputs are off. Units with a two position system 
switch or without a system switch must use a load transfer 
switch when both heating and cooling outputs are used. This 
prevents control failure and equipment damage caused by 
direct cycling between loads.

TB155: An ON-OFF system switch enables auto-changeover 
of heating and cooling modes. In the ON position the 
thermostat activates heating or cooling outputs dependant 
upon the relationship between set point and ambient 
temperature. Heat on to cool on dead band is 4°F. In the OFF 
position, heating and cooling outputs are off. Units without a 
system switch cycle between heating and cooling with a 4°F 
dead band.

FAN: Some units have a switch for manual selection of fan 
speed. On these units fan operation is either internally wired 

Installation and Maintenance Manual

IM 1014

MT 155 Thermostat

Group: 

Applied Air Systems

Part Number: 910102989

Date: 

August 2009

DANGER

READ THESE INSTRUCTIONS CAREFULLY BEFORE 
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
THERMOSTAT.

Failure to observe safety information and comply with 
instructions could result in PERSONAL INJURY, DEATH AND/ 
OR PROPERTY DAMAGE.

To avoid electrical shock or damage to equipment, disconnect 
power before installing or servicing. Use only wiring with 
insulation rated for full thermostat operating voltage. Use 
copper wire only. Insulate or wirenut all un-used leads. Any 
wiring, including the remote probe,may carry the full operating 
voltage of the thermostat.

To avoid potential fire and/ or explosion do not use in 
potentially flammable or explosive atmospheres.

Retain these instructions for future reference. You must review 
your application and national and local codes to ensure that 
your installation will be functional and safe.

INSTALL COVER

LOCKING SCREW

REMOVE JP1

WHEN USING A

REMOTE SENSOR

JP1

Отзывы: