Keypad/Display Menu Structure
* Max Heat Rise represents positions 12, 13 and 14 of the Software Configuration Code.
Save/Restore Menu
The Save/Restore menu can be used to save or restore the user configured parameters as well
as reset the controller back to the factory default parameters.
17
Return/Exhaust Fan
Capacity Control
Method
0 = None
•
1 = Tracking
2 = Building Pressure
3 = Position
18
Second Duct
Pressure Sensor
0 = No
•
•
1 = Yes
19
Entering Fan Temp
Sensor
0 = No
•
1 = Yes
20
Energy Recovery
0 = None
•
1=ConstSpdWhl
2=VarSpdWhl/Grhm
3=VarSpdWhl/McQ21
21
Cooling Circuit Type
0 = Individual
•
•
1 = Dual Circ. Water Condenser
2 = Dual Circ. Air Condenser
22
Head Pressure
Control
0 = No
•
1 = Yes
23
Bypass Valve Control
0 = Slave
•
1 = Bypass
24, 25, 26
Unit Size
Three digits
(default 050)
•
•
27
Refrigerant Type
0 = R22
•
•
1 = R407C
2 = R410A
28
Reheat Type
0 = None
•
1 = StgHG
2 = ModHG
3 = STdHtRht
Table 44: Save/Restore Menu
Menu Display Name Item Display Name
Default Setting
Range
Password Level
Save/Restore
Save Params=
No
No/Yes
2
Rstr Params=
No
No/Yes
2
Rstr Factory=
No
No/Yes
2
Table 43: Unit Configuration Menu
Configuration
Code Position
Description
Values (Default Bold)
RTU
SCU