Keypad/Display Menu Structure
Head Pressure Setup Menu
Head Press DB
is an adjustable item that sets a deadband around the Head Pressure Setpoint
parameter.
WRV Period
is an adjustable item which sets the “sampling time” used in the PI control
function of the water regulating valve.
WRV Gain
is an adjustable item which sets the “proportional band” used in the PI control
function of the water regulating valve.
WRV PAT
is an adjustable item which sets the “project ahead” used in the PI control function
of the water regulating valve.
WRV Max Chg
is an adjustable item that sets the maximum value for an increase or decrease
of the water regulating valve.
Init Op Time
The first compressor runs for an editable Initial Operation Time (InitOpTime)
with the WRV at an initial start up position (InitPos).
Min WRV Pos
is an adjustable item used which sets the minimum WRV position (default
10%).
Min WRV Tmp
is an adjustable item which is used to set the edited temperature where WRV
at a minimum position is OK.
Max WRV Tmp
is an adjustable item which is used to set the edited temperature where WRV
at 100% is OK.
WRV Act Time
is an adjustable item which is used to set the time required for the WRV to be
driven from 0 to 100%.
Min WRV Time
is an adjustable item which sets the minimum WRV time (default 60
seconds.
Chilled Water Setup Menu
Clg DB
an adjustable item which sets a dead band around the discharge cooling setpoint
parameter. For example, if the discharge cooling setpoint parameter is set to 55ºF and the Clg
Db parameter is set to 2ºF the dead band around the set point would be from 56.0ºF to 54.0ºF.
Table 31: Head Pressure Setup Menu
Menu Display Name Item Display Name
Default Setting
Range
Password Level
Head Press Setup
Head Press DB=
10psi
0-50psi
4
WRV Period=
10s
0-999s
4
WRV Gain=
3.6
0.0-100.0
4
WRV PAT=
10s
0-999s
4
WRV Max Chg=
7%
0-100%
4
Init Op Time=
60s
0-3600s
4
Min WRV Pos=
10%
0-100%
4
Min WRV Tmp=
58°F
20-150°F
4
Max WRV Tmp=
105°F
20-150°F
4
WRV Act Time=
60s
0-300s
4
Min WRV Time=
60s
0-3600s
4
Table 32: Chilled Water Setup Menu
Menu Display Name Item Display Name
Default Setting
Range
Password Level
Chilled Water Setup
Clg DB=
2.0°F
1.0-10.0°F
4
Clg Period=
20s
0-999s
4
Clg Gain=
1
0.0-100.0
4
Clg PAT=
40s
0-999s
4
CW Max Chg=
15%
0-100%
4
Stage Time=
5min
5-60min
4
OAT Clg Lock=
55°F
0-100°F
4
OATDiff=
2°F
0-10°F
4