McQuay OM 920-1
Keypad/Display Menu Structure
Compressor Setup Menu
Clg DB
is an adjustable item which sets a dead band around the discharge cooling setpoint
parameter. For example, if the discharge cooling setpoint parameter is set to 55ºF and the Clg
Db parameter is set to 2ºF the dead band around the set point would be from 56.0ºF to 54.0ºF.
Lead Circuit
is an adjustable item used to set which circuit will be the Lead Circuit.
Staging Type
is an adjustable item used to set the type of compressor staging to be used. If
dehumidification is active, Alternate Staging is used regardless of the Staging Type setting.
Stage Time
is an adjustable item used to set a minimum time period between compressor
stage changes.
CfanOut1 Spt
is an adjustable item used to set the OAT temperature that the first “controlled”
condenser fan stage on each circuit has turned on. The first controlled condenser fan output is
turned on when any compressor is on and the OAT rises above the Condenser Stage 1 Set
Point. The first controlled condenser fan output is turned off when all compressors are off or
the OAT drops below the Condenser Stage 1 Set Point by more than the Condenser Fan
Differential (Default = 55°F).
CfanOut2 Spt
is an adjustable item used to set the OAT temperature that the second
“controlled” condenser fan stage on each circuit has turned on. The second controlled
condenser fan output is turned on when any compressor is on and the OAT rises above the
Condenser Stage 2 Set Point. The second controlled condenser fan output is turned off when
all compressors are off or the OAT drops below the Condenser Stage 2 Set Point by more than
the Condenser Fan Differential (Default = 65°F).
CfanOut3 Spt
is an adjustable item used to set the OAT temperature that the third
“controlled” condenser fan stage on each circuit has turned on. The third controlled condenser
fan output is turned on when any compressor is on and the OAT rises above the Condenser
Stage 3 Set Point. The third controlled condenser fan output is turned off when all
compressors are off or the OAT drops below the Condenser Stage 3 Set Point by more than the
Condenser Fan Differential (Default = 65°F)
Cond Fan Diff
is an adjustable item to set the Condenser Fan Differential (Default = 5°F).
OAT Clg Lock
is an adjustable item which sets the low outdoor air temperature mechanical
cooling lockout point. Mechanical cooling operation is disabled when the outdoor air
temperature sensor input falls below this set point.
OATDiff
is an adjustable item which sets a differential above the OAT Clg Lock parameter.
Mechanical cooling operation is re-enabled when the outdoor air temperature sensor input
rises above the OAT Clg Lock value by more than this differential.
Min EWT
is an adjustable item that sets the minimum allowable entering water temperature.
Mechanical Cooling is disabled when the entering water temperature sensor input falls below
this setpoint
Table 30: Compressor Setup Menu
Menu Display Name Item Display Name
Default Setting
Range
Password Level
Compressor Setup
Clg DB=
2.0°F
1.0-10.0°F
4
Lead Circuit=
#1
Auto
4
#1
#2
Staging Type=
Standard
Standard
4
Alternate
Stage Time=
5min
5-60min
4
CFanOut1 Spt=
55°F
0-105°F
4
CFanOut2 Spt=
65°F
0-105°F
4
CFanOut3 Spt=
75°F
0-105°F
4
Cond Fan Diff=
5°F
5-20°F
4
OAT Clg Lock=
55°F
0-100°F
4
OATDiff=
2°F
0-10°F
4
Min EWT=
55°F
20-100°F
4