R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
79
5.Test Operation
(1) The test operation must be carried out after the entire installation has been completed.
(2) Please confirm the following points before the test operation.
⚫
The indoor unit and outdoor unit are installed properly.
⚫
Tubing and wiring are correctly completed.
⚫
The refrigerant pipe system is leakage-checked.
⚫
The drainage is unimpeded.
⚫
The ground wiring is connected correctly.
⚫
The length of the tubing and the added stow capacity of the refrigerant have been recorded.
⚫
The power voltage fits the rated voltage of the air conditioner.
⚫
There is no obstacle at the outlet and inlet of the outdoor and indoor units.
⚫
The gas-side and liquid-side stop values are both opened.
⚫
The air conditioner is pre-heated by turning on the power.
(3) According to the user's requirement, install the remote controller when the remote controller's signal
can reach the indoor unit smoothly.
(4) Test operation
Set the air conditioner under the mode of "COOLING" with the remote controller, and check the following
points.
Indoor unit
⚫
Whether the switch on the remote controller works well.
⚫
Whether the buttons on the remote controller works well.
⚫
Whether the air flow louver moves normally.
⚫
Whether the room temperature is adjusted well.
⚫
Whether the indicator lights normally.
⚫
Whether the temporary buttons works well.
⚫
Whether the drainage is normal.
⚫
Whether there is vibration or abnormal noise during operation.
Outdoor unit
⚫
Whether there is vibration or abnormal noise during operation.
⚫
Whether the generated wind, noise, or condensed of by the air conditioner have influenced your
neighborhood.
⚫
Whether any of the refrigerant is leaked.
Содержание MCI16036CCU216A
Страница 12: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 12 Operation temp C 16 32 16 32...
Страница 14: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 14 3 Service Space...
Страница 15: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 15 4 Wiring Diagrams...
Страница 16: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 16...
Страница 23: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 23 1 E4 E5 E6 T4 T5 T3 temperature sensors error...
Страница 25: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 25 4 E12 IPM modular sensor error...
Страница 26: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 26 5 E13 HLP Pressure sensor error...
Страница 27: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 27 6 E14 H8 H12 T3 or T5 sensor disconnect error...
Страница 28: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 28 7 E15 High pressure switch error...
Страница 41: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 41 1 3 Dimension MQC164036CCK216B MQC164060CCK216B...
Страница 60: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 60 2 7 Exploded View 2 7 1 MQC164036CFC216B...
Страница 63: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 63 2 7 2 MQC164060CFC216B...
Страница 81: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 81 16 seer Outdoor with Duct...
Страница 82: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 82 16 seer Outdoor with Floor Ceiling...
Страница 83: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 83 16 seer Outdoor with 10 seer AHU...