R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual
77
4. Insulation Work
4.1 Insulation material and thickness
4.1.1. Insulation material
Insulation material should adopt the material which is able to endure the pipe’s temperature: no less than 70
℃
in the high-pressure side, no less than 120
℃
in the low-pressure side(For the cooling type machine, no
requirements at the low-pressure side.)
◆
Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above 120
℃
)
Cooling only type----Polyethylene foam (withstand above 100
℃
)
4.1.2. Thickness choice for insulation material
Insulation material thickness is as follows:
Pipe diameter (mm)
Adiabatic material thickness
Refrigerant pipe
Φ6.4—Φ25.4
10mm
Φ28.6—Φ38.1
15mm
Drainage pipe
Inner diameterΦ20—Φ32
6mm
4.2 Refrigerant pipe insulation
4.2.1. Work Procedure
①
Before laying the pipes, the non-jointing parts and non-connection parts should be heat insulated.
②
When the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat
insulated.
4.2.2. Insulation for non-jointing parts and non-connection parts
wrong
right
Gas pipe and liquid pipe should
not be put together to insulate
Insulate the gas pipe
(cooling only)
Insulate the gas pipe and
liquid pipe
Содержание MCI16036CCU216A
Страница 12: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 12 Operation temp C 16 32 16 32...
Страница 14: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 14 3 Service Space...
Страница 15: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 15 4 Wiring Diagrams...
Страница 16: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 16...
Страница 23: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 23 1 E4 E5 E6 T4 T5 T3 temperature sensors error...
Страница 25: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 25 4 E12 IPM modular sensor error...
Страница 26: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 26 5 E13 HLP Pressure sensor error...
Страница 27: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 27 6 E14 H8 H12 T3 or T5 sensor disconnect error...
Страница 28: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 28 7 E15 High pressure switch error...
Страница 41: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 41 1 3 Dimension MQC164036CCK216B MQC164060CCK216B...
Страница 60: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 60 2 7 Exploded View 2 7 1 MQC164036CFC216B...
Страница 63: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 63 2 7 2 MQC164060CFC216B...
Страница 81: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 81 16 seer Outdoor with Duct...
Страница 82: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 82 16 seer Outdoor with Floor Ceiling...
Страница 83: ...R410A 60Hz 16 SEER Universal Outdoor Series Technical Manual 83 16 seer Outdoor with 10 seer AHU...