67
The most common causes of air conditioner failure to “start" are:
a) Voltage not within
±
10% of rated voltage.
b) Power supply interrupted.
c) Control settings improper.
d) Air conditioner is disconnected from main power source.
e) Fuse blown or circuit breaker off.
ii) Diagnosis Of Refrigerant Circuit / Application
There might be some cases where the unit starts running but does not perform satisfactory, i.e.
insufficient cooling. Judgement could be made by measuring temperature difference of indoor
unit's intake and discharge air as well as running current.
Insufficient Cooling
Unit Starts
Excessive heat
source e.g. electric
kettle
High heat load
Refrigerant circuit
Leakage
Restriction e.g. at
strainer, capillary,
filter dryer, etc.
Compressor
Less or no compression
(Low running current)
Room overcrowded
with people
Windows / doors
wide open
Check air circulation
Indoor/Outdoor coil dirty
(clogged)
Air filters dirty
Fan Malfunction
Obstruction at air inlet/outlet
of indoor/outdoor unit
Satisfactory operation with temperature difference of
air intake & discharge of indoor unit 10°C - 15°C
Insufficient Heating
Unit Starts
High heat load
Refrigerant circuit
Leakage
Restriction e.g. at
strainer, capillary,
filter dryer, etc.
Compressor
Less or no compression
(Low running current)
Windows / doors
wide open
Check air circulation
Indoor/Outdoor coil dirty (clogged)
Air filters dirty
Fan Malfunction
Obstruction at air inlet/outlet
of indoor/outdoor unit
Satisfactory operation with temperature difference of
air intake & discharge of indoor unit 16°C - 25°C
Содержание MCC 010C/CR
Страница 16: ...15 Model MCC050C Model MCC060C...
Страница 26: ...25 Model MCC 060 MLC 060C For export spec with MC Model MCC 060C MLC 060C For local spec...
Страница 27: ...26 Model MCC 060C MMC 060C For export spec with SLM control C3 0BCC...
Страница 28: ...27 Model MCC 010CR 015CR MLC M4LC 010BR 015BR...
Страница 29: ...28 Model MCC 020CR 025CR MLC M4LC 020BR 025BR...
Страница 30: ...29 Model MCC 030CR MLC M4LC 030CR...
Страница 31: ...30 Model MCC 040CR 050CR MLC M4LC 040CR 050CR...
Страница 32: ...31 Model MCC 060CR MLC 060CR...
Страница 33: ...32 Model MCC 060CR MMC 060CR For export spec with SLM control C3 0BCC...
Страница 37: ...36 Model MCC 060C MMC 060C For export spec with SLM control U1 4...
Страница 38: ...37 Model MCC 010 015CR MLC M4LC 010 015BR For export spec with SLM control U1 4...
Страница 39: ...38 Model MCC 020 025CR MLC M4LC 020 025BR For export spec with SLM control U1 4...
Страница 40: ...39 Model MCC 030CR MLC M4LC 030CR For export spec with SLM control U1 4...
Страница 41: ...40 Model MCC 040 050CR MLC M4LC 040 050CR For export spec with SLM control U1 4...
Страница 42: ...41 Model MCC 060CR MLC 060CR For export spec with SLM control U1 4...
Страница 43: ...42 Model MCC 060CR MMC 060CR For export spec with SLM control U1 4...
Страница 46: ...45 Model MLC 020 025BR Heat pump 3 Phase 50Hz 380 415V Model MLC 030CR Heat pump 3 Phase 50Hz 380 415V...
Страница 49: ...48 Low Ambient Unit Optional Outdoor Unit Model MLC 010B 015B 50Hz Outdoor Unit Model MLC 020B 025B 50Hz...