57
Additional Charge
•
The refrigerant gas has already charged into the outdoor unit. For the piping length of 5m. Additional refrigerant
charge after vacuuming is not necessary.
•
When the piping length is more than 5m, please use the table below (unit in gram).
Cooling
MODEL
MCC010C
MCC015C
MCC020C
MCC025C
MCC030C
MCC040C
MCC050C
MCC060C
7m
30
30
30
76
100
100
100
100
10m
75
75
75
190
250
250
250
250
15m
-
-
150
380
500
500
500
500
20m
-
-
-
-
750
750
750
750
35m
-
-
-
-
1500
1500
1500
1500
Heat pump
MODEL
MCC010CR
MCC015CR
MCC020CR
MCC025CR
MCC030CR
MCC040CR
MCC050CR
MCC060CR
7m
40
40
50
100
100
100
100
100
10m
100
100
125
250
250
250
250
250
15m
-
-
250
500
500
500
500
500
20m
-
-
-
-
750
750
750
750
35m
-
-
-
-
1500
1500
1500
1500
Overall Checking
•
Ensure the following, in particular :
1) The unit is mounted solidly and rigid in position.
2) Piping and connections are leak proof after charging.
3) Proper wiring has been done.
•
Drainage check - pour some water into drain pan.
•
Test run
1) Conduct a test run after water drainage test and gas leakage test.
2) Watch out for the following :
a) Is the electric plug firmly inserted into the socket?
b) Is there any abnormal sound from unit?
c) Is there any abnormal vibrations with regard to unit itself or piping?
d) Is there smooth drainage of water?
•
Check that :
1) Outdoor fan is running, with warm air blowing off the outdoor unit (cooling cycle).
2) Indoor blower is running and discharge cool air (cooling cycle).
3) Suction (low side) pressure as recommended is before this.
4) The remote controller incorporate a 3 minute delay in there circuit. Thus, it requires about 3
minutes before the outdoor unit can start up.
CAUTION FOR R407C
Do not top-up when servicing leak, as this will reduce the unit performance. Vacuum the unit
thoroughly and then charge the unit with fresh R407C according to the amount recommended
in the specification.
CAUTION FOR R407C
Avoid prolong exposure of an opened compressor, or the internal part of refrigerant piping to moist air.
The POE oil in the compressor and piping can absorb moisture from air.
Содержание MCC 010C/CR
Страница 16: ...15 Model MCC050C Model MCC060C...
Страница 26: ...25 Model MCC 060 MLC 060C For export spec with MC Model MCC 060C MLC 060C For local spec...
Страница 27: ...26 Model MCC 060C MMC 060C For export spec with SLM control C3 0BCC...
Страница 28: ...27 Model MCC 010CR 015CR MLC M4LC 010BR 015BR...
Страница 29: ...28 Model MCC 020CR 025CR MLC M4LC 020BR 025BR...
Страница 30: ...29 Model MCC 030CR MLC M4LC 030CR...
Страница 31: ...30 Model MCC 040CR 050CR MLC M4LC 040CR 050CR...
Страница 32: ...31 Model MCC 060CR MLC 060CR...
Страница 33: ...32 Model MCC 060CR MMC 060CR For export spec with SLM control C3 0BCC...
Страница 37: ...36 Model MCC 060C MMC 060C For export spec with SLM control U1 4...
Страница 38: ...37 Model MCC 010 015CR MLC M4LC 010 015BR For export spec with SLM control U1 4...
Страница 39: ...38 Model MCC 020 025CR MLC M4LC 020 025BR For export spec with SLM control U1 4...
Страница 40: ...39 Model MCC 030CR MLC M4LC 030CR For export spec with SLM control U1 4...
Страница 41: ...40 Model MCC 040 050CR MLC M4LC 040 050CR For export spec with SLM control U1 4...
Страница 42: ...41 Model MCC 060CR MLC 060CR For export spec with SLM control U1 4...
Страница 43: ...42 Model MCC 060CR MMC 060CR For export spec with SLM control U1 4...
Страница 46: ...45 Model MLC 020 025BR Heat pump 3 Phase 50Hz 380 415V Model MLC 030CR Heat pump 3 Phase 50Hz 380 415V...
Страница 49: ...48 Low Ambient Unit Optional Outdoor Unit Model MLC 010B 015B 50Hz Outdoor Unit Model MLC 020B 025B 50Hz...