Wall Mounted Split Systems

Models: MWM009J/JR

MWM015J/JR

M5WM010J/JR
M5WM015J/JR

Catalog

MWM - J - 2009

Cover.indd   1

Cover.indd   1

3/6/2009   6:06:22 PM

3/6/2009   6:06:22 PM

Содержание M5WM010J

Страница 1: ...Wall Mounted Split Systems Models MWM009J JR MWM015J JR M5WM010J JR M5WM015J JR Catalog MWM J 2009...

Страница 2: ......

Страница 3: ...ions at any time without notice Table of Contents Nomenclature 1 Indoor Unit 1 Outdoor Unit 2 Product Line Up 3 Features 7 Application Information 8 Operating Range 8 Refrigerant Circuit Diagram 9 Con...

Страница 4: ...e Indoor Unit M 5 WM 010 J R Brand M Mcquay Refrigerant 4 5 Omitted if R22 R407C R410A Model Name WM Wall Mounted Capacity Index 010 015 10 000 Btu h 15 000 Btu h Series G J G Series J Series Model Ty...

Страница 5: ...Unit M 5 LC 010 C R Brand M Mcquay Refrigerant 4 5 Omitted if R22 R407C R410A Model Name LC Single Split Condensing Unit Capacity Index 010 015 10 000 Btu h 15 000 Btu h Series C C Series Model Type R...

Страница 6: ...PCB Handset Air Purifi cation Grille Marking Others LGSN G17 Saranet Filter Bio Filter A CE COOLING ONLY 009J ACBAA X X X X X X 009J ACLAA X X X X X 015J ACBAA X X X X X X 015J ACLAA X X X X X HEATPU...

Страница 7: ...ndset Air Purifi cation Grille Marking Others LGSN G17 Saranet Filter Bio Filter A CE COOLING ONLY 010J ACBAA X X X X X X 010J ACLAA X X X X X 015J ACBAA X X X X X X 015J ACLAA X X X X X HEATPUMP 010J...

Страница 8: ...tion PCB Refrigerant Control FIN Safety Devices Compressor Marking Others Cap Tube EXV Gold Coated Blue Coated Bare Contactor HP LP Rotary CE Drain Elbow Low Ambient Kit COOLING ONLY 009C ACPOH X X X...

Страница 9: ...nt Control FIN Safety Devices Compressor Marking Others Cap Tube EXV Gold Coated Blue Coated Bare Contactor HP LP Rotary CE Drain Elbow Low Ambient Kit COOLING ONLY 010C ACPGG X X X X X 010C ACPOG X X...

Страница 10: ...is installed and sharing the same phase of power Wireless Remote Controller The compact LCD transmitter is able to operate the air conditioner unit within the distance of 8 meters Fan speed can be set...

Страница 11: ...to local dealer for unit of this specification Indoor temp CDB Cooling Outdoor temp CDB Indoor temp CWB Outdoor temp CDB Indoor temp CWB Heating Outdoor temp CWB 9 16 21 6 30 5 19 35 14 46 23 Standar...

Страница 12: ...Information MWM J 2009 70034 049971 Refrigerant Circuit Diagram Model MWM009J MLC009C M5WM010J M5LC010C MWM015J MLC015C M5WM015J M5LC015C 70034 023154 Model MWM009JR MLC009CR M5WM010JR M5LC010CR M5WM0...

Страница 13: ...10 MWM J 2009 Application Information 70034 095236 Model MWM015JR MLC015CR...

Страница 14: ...under COOL HEAT and AUTO mode When the unit is operating under cooling mode the set temperature is increased by 0 5 C after 30 minutes 1 C after an hour and 2 C after 2 hours When the unit is operati...

Страница 15: ...t or damage to the compressor Ensure that the unit s panel is closed after service or installation Unsecured panels will cause the unit to operate noisily Sharp edges and coil surfaces are potential l...

Страница 16: ...out the service lid diagonally down in thedirection of the arrow 1 Pull down 250mm from wall Caution Before installing the unit ensure that the power supply matches the power requirement of the air co...

Страница 17: ...ting tape Right bottom piping Remove pipe port cover here for right bottom piping Right side piping Remove pipe port cover here for right side piping Remove pipe port cover here for left bottom piping...

Страница 18: ...Hole with cone drill Mounting Unit onto the Installation Plate Hook the indoor unit onto the upper portion of the installation plate engage the two hooks at the rear top of the indoor unit with the up...

Страница 19: ...p Unit Only There are 2 holes on the base of outdoor unit for condensed water to flow out Insert the drain elbow to one of the holes To install the drain elbow first insert one portion of the hook to...

Страница 20: ...unit can draw in and distribute plenty of air thus lowering the condensing temperature A place capable of bearing the weight of the outdoor unit and isolating noise and vibration A place protected fr...

Страница 21: ...ot refrigerant piping compressor or any moving parts of fan motors Refrigerant Piping Piping Length and Elevation When the pipe length becomes too long both the capacity and reliability drop As the nu...

Страница 22: ...Remove burr Insert the flare nuts mounted on the connection parts of both the indoor unit and outdoor unit onto the copper pipes Flare the pipe with extra length above the flaring tool as shown in th...

Страница 23: ...r lower Evacuation time varies by the pump but averagely in 1 hour Filter Dryer Mclecular Sieve Type Note R22 Nil R410A Nil 4 After evacuation unscrew the spindle diagram B for the gas to run to indoo...

Страница 24: ...ere any abnormal vibration with regard to the unit itself or piping d Is there smooth drainage of water Check that 1 Outdoor fan is running with warm air blowing off the outdoor unit cooling cycle 2 I...

Страница 25: ...ore easily affected by dust of moisture compared with R22 make sure to temporarily cover the ends of the tubing prior to installation Compressor oil No additional charge of compressor oil is permitted...

Страница 26: ...R410A is being delivered into the system The liquid composition can be different from the vapor composition Dip pipe Liquid withdrawal Invert cylinder without dip pipe e Normally the R410A cylinder o...

Страница 27: ...22 18 19 11 28 22 M5WM010J JR High 31 35 36 34 30 22 9 38 33 Medium 26 30 31 27 22 13 5 32 25 Low 24 26 27 22 15 7 7 27 21 S Low 23 24 25 20 13 6 5 25 MWM015J JR M5WM015J JR High 32 35 36 34 31 22 11...

Страница 28: ...y Hz Sound pressure level dB ref20 Pa High Fan NC 30 NC 35 NC 40 NC 45 Low Fan Medium Fan NC 25 NC 20 S Low Fan M5WM010J JR NC CURVES 0 10 20 30 40 50 60 125 250 500 1000 2000 4000 8000 Octave band fr...

Страница 29: ...ata MWM015J JR M5WM015J JR NC CURVES 0 10 20 30 40 50 60 125 250 500 1000 2000 4000 8000 Octave band frequency Hz Sound pressure level dB ref20 Pa High Fan Medium Fan Low Fan NC 20 NC 30 NC 45 NC 40 N...

Страница 30: ...DIMENSION HEIGHT mm in 350 13 8 350 13 8 WIDTH mm in 874 34 4 874 34 4 DEPTH mm in 280 11 0 280 11 0 UNIT WEIGHT kg lb 12 26 5 12 26 5 CONDENSATE DRAIN SIZE mm in 16 0 6 16 0 6 OUTDOOR UNIT AIR FLOW...

Страница 31: ...800 31 5 800 31 5 DEPTH mm in 204 8 0 204 8 0 PACKING DIMENSION HEIGHT mm in 350 13 8 350 13 8 WIDTH mm in 874 34 4 874 34 4 DEPTH mm in 280 11 0 280 11 0 UNIT WEIGHT kg lb 12 26 5 12 26 5 CONDENSATE...

Страница 32: ...ON HEIGHT mm in 350 13 8 350 13 8 WIDTH mm in 874 34 4 874 34 4 DEPTH mm in 280 11 0 280 11 0 UNIT WEIGHT kg lb 12 26 5 12 26 5 CONDENSATE DRAIN SIZE mm in 16 0 6 16 0 6 OUTDOOR UNIT AIR FLOW l s CFM...

Страница 33: ...m in 800 31 5 800 31 5 DEPTH mm in 204 8 0 204 8 0 PACKING DIMENSION HEIGHT mm in 350 13 8 350 13 8 WIDTH mm in 874 34 4 874 34 4 DEPTH mm in 280 11 0 280 11 0 UNIT WEIGHT kg lb 12 26 5 12 26 5 CONDEN...

Страница 34: ...INNER GROOVE COPPER DIAMETER mm in 7 00 0 276 7 00 0 276 THICKNESS mm in 0 28 0 011 0 28 0 011 FIN MATERIAL ALUMINIUM HYDROPHILIC FIN ALUMINIUM HYDROPHILIC FIN THICKNESS mm in 0 11 0 004 0 11 0 004 FA...

Страница 35: ...NNER GROOVE COPPER DIAMETER mm in 7 00 0 276 7 00 0 276 THICKNESS mm in 0 28 0 011 0 28 0 011 FIN MATERIAL ALUMINIUM HYDROPHILIC FIN ALUMINIUM HYDROPHILIC FIN THICKNESS mm in 0 11 0 004 0 11 0 004 FAC...

Страница 36: ...LESS INNER GROOVE COPPER DIAMETER mm in 7 00 0 276 7 00 0 276 THICKNESS mm in 0 28 0 011 0 28 0 011 FIN MATERIAL ALUMINIUM HYDROPHILIC FIN ALUMINIUM HYDROPHILIC FIN THICKNESS mm in 0 11 0 004 0 11 0 0...

Страница 37: ...S INNER GROOVE COPPER DIAMETER mm in 7 00 0 276 7 00 0 276 THICKNESS mm in 0 28 0 011 0 28 0 011 FIN MATERIAL ALUMINIUM HYDROPHILIC FIN ALUMINIUM HYDROPHILIC FIN THICKNESS mm in 0 11 0 004 0 11 0 004...

Страница 38: ...r WB column 15 C only available in the case of Indoor DB 20 C Thus Extrapolation between 16 C WB and 17 C WB during 24 C indoor DB is required 3 Refer to the Outdoor DB column 37 C is located between...

Страница 39: ...y SC Extrapolation Method 17 C 15 C 1 640kW y1 17 C 16 C 1 640kW 1 727kW y1 1 814kW b Indoor Condition 24 C DB 15 C WB Outdoor Condition 40 C DB Indoor DB C Indoor WB C Outdoor DB C 40 TC kW SC kW 24...

Страница 40: ...ation Method 24 C 20 C 1 814kW 1 181kW 24 C 23 C 1 814kW y3 y1 1 656kW b Indoor Condition 23 C DB 15 C WB Outdoor Condition 40 C DB Indoor DB C Indoor WB C Outdoor DB C 40 TC kW SC kW 20 15 2 131 0 96...

Страница 41: ...utdoor Condition 37 C DB Indoor DB C Indoor WB C Outdoor DB C 35 37 40 TC kW SC kW TC kW SC kW TC kW SC kW 23 15 2 368 1 656 x y 2 131 1 439 Total capacity TC Interpolation Method 40 C 35 C 2 131kW 2...

Страница 42: ...2 816 1 966 2 679 1 935 2 541 1 903 2 377 1 865 24 3 092 1 855 2 970 1 841 2 847 1 826 2 725 1 811 2 602 1 796 2 455 1 778 Model MWM015J MLC015C Cooling Mode ID DB C ID WB C Outdoor DB C 20 25 30 35...

Страница 43: ...23 3 091 1 713 2 953 1 681 2 816 1 650 2 679 1 618 2 541 1 587 2 377 1 549 24 3 092 1 539 2 970 1 524 2 847 1 509 2 725 1 495 2 602 1 480 2 455 1 462 30 20 3 085 2 552 2 904 2 470 2 722 2 388 2 541 2...

Страница 44: ...23 4 908 2 304 4 602 2 236 4 296 2 168 3 990 2 101 3 685 2 033 3 318 1 952 24 5 029 2 114 4 725 2 061 4 422 2 009 4 118 1 957 3 814 1 905 3 450 1 842 30 20 4 543 3 219 4 231 3 104 3 919 2 989 3 608 2...

Страница 45: ...6 3 051 2 024 2 836 1 831 2 621 1 639 2 363 1 408 24 3 540 2 269 3 322 2 063 3 105 1 857 2 887 1 650 2 670 1 444 2 409 1 196 Model M5WM015J M5LC015C Cooling Mode ID DB C ID WB C Outdoor DB C 20 25 30...

Страница 46: ...9 23 3 481 2 087 3 266 1 895 3 051 1 702 2 836 1 510 2 621 1 318 2 363 1 087 24 3 540 1 948 3 322 1 741 3 105 1 535 2 887 1 329 2 670 1 122 2 409 0 875 30 20 3 303 2 825 3 096 2 675 2 889 2 525 2 681...

Страница 47: ...0 23 4 146 2 369 3 898 2 171 3 651 1 974 3 403 1 776 3 156 1 578 2 859 1 341 24 4 213 2 189 3 963 1 974 3 714 1 760 3 464 1 545 3 214 1 330 2 915 1 072 30 20 3 943 3 245 3 703 3 099 3 463 2 953 3 222...

Страница 48: ...VER 50123456789 Note Dimension in mm Outdoor Unit Model MLC009 015C CR M5LC010 015C CR 3 1 0 B F E N C N K L L M 30 2 1 A D 19 7 0 C G H I J O 80 3 1 65 2 6 Dimension A B C D E F G H I J K L M N O 10...

Страница 49: ...ER WITHOUT PRIOR NOTICE 2 ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 Electrical Data Heat Pump R22 MODEL INDOOR UNIT MWM009JR MWM015JR OUTDOOR UNIT MLC009CR MLC015CR INDOOR MOTOR INSULATION GRA...

Страница 50: ...HOUT PRIOR NOTICE 2 ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 Electrical Data Heat Pump R410A MODEL INDOOR UNIT M5WM010JR M5WM015JR OUTDOOR UNIT M5LC010CR M5LC015CR INDOOR MOTOR INSULATION GRA...

Страница 51: ...48 MWM J 2009 Wiring Diagram Wiring Diagram Cooling Only Indoor Unit Outdoor Unit Model MWM009 015J Model MLC009 015C M5WM010 015J M5LC010 015C 70034 101945...

Страница 52: ...49 Wiring Diagram MWM J 2009 70034 101944 Heat Pump Indoor Unit Outdoor Unit Model MWM009 015JR Model MLC009 015CR M5WM010 015JR M5LC010 015CR...

Страница 53: ...flow through the indoor or outdoor Every month Power Supply 1 Check the running current and voltage for indoor and outdoor unit 2 Check the electrical wiring and tighten the wire onto the terminal blo...

Страница 54: ...mal circumstances these outdoor units only require a check and cleaning of air intake coil surface once every 3 months However if a unit is installed in areas subjected to much oil mist and dust the c...

Страница 55: ...h 4 Discharge airflow has bad odor Cigarettes smoke particles perfume and others which might have adhered onto the coil may cause odor Contact your nearest dealer 5 Condensation on the front air grill...

Страница 56: ...ression no compression compressor defective 2 Reversing valve leaking High side Low side 1 Undercharged with refrigerant 2 Refrigerant leakage 3 Air filter clogged dirty indoor unit 4 Indoor fan locke...

Страница 57: ...to 3 phase model Faulty Blown Tripped Coil burned Contact faulty Faulty Faulty fan motor Defective operation switch Evaporator fan contactor Over current relay for evaporator fan Fuse for operation ci...

Страница 58: ...contactor Repair or change if necessary Change the contactor Change the compressor Change the contacts Correct the wiring Contact faulty Other electrical component faulty Evaporator contactor The most...

Страница 59: ...nt circuit High cooling load Air circulation Clean the coil Clean the filter Fan motor malfunction Change or repair the motor Obstruction at air inlet outlet of indoor outdoor unit Remove the obstruct...

Страница 60: ...ction Change or repair the motor Obstruction at air inlet outlet of indoor outdoor unit Remove the obstruction Windows doors wide open Close the windows doors Refrigerant short charge or refrigerant l...

Страница 61: ...Others 1 Short Beep Cooling Unit Heat Pump Unit The table below shows the LED indicator lights for the air conditioner unit under normal operation and fault conditions The LED lights are located at t...

Страница 62: ...e on Dry mode on 1 time Blink E1 Room air sensor contact loose short 3 times Blink E3 Outdoor coil sensor open 2 times Blink E2 Indoor coil sensor open 1 time Blink E4 Compressor overload indoor coil...

Страница 63: ...loded View and Part List INDOOR UNIT MODEL MWM009 015J JR M5WM010 015J JR 70024102581 Note All exploded view and part list are subjected to change by the manufacturer without prior notice 1 2 3 8 10 1...

Страница 64: ...unting Plate 1 R12014095347 10 Motor Mounting Plate 2 R12014095348 11 Blower R03029030446 12 Assy Installation Plate R50014095316 13 Right Side Panel R12014095332 14 Cover Drip Proof R12014095349 15 C...

Страница 65: ...Cap Tube R50024100896 7 Bracket Fan Motor R01014052516 8 Fan Motor R03039028206 9 Fan Blade R03019020744 10 Left Panel R01014052510Y 11 Right Panel R01014084434Y 12 Assy Front Panel R01014052512 No D...

Страница 66: ...63 Exploded View and Part List MWM J 2009 OUTDOOR UNIT MODEL MLC015C M5LC010 015C 70024056771 Note All exploded view and part list are subjected to change by the manufacturer without prior notice...

Страница 67: ...5C R03039015323 M5LC010C R03039016104 M5LC015C R03039015323 9 Fan Blade R03019015339 10 Left Panel R01014051166Y 11 Right Panel R01014051167Y 12 Assy Front Panel R01014051171Y No Description Part Numb...

Страница 68: ...65 Exploded View and Part List MWM J 2009 OUTDOOR UNIT MODEL MLC009CR 70024061683 Note All exploded view and part list are subjected to change by the manufacturer without prior notice...

Страница 69: ...50024102031 8 Bracket Fan Motor R01014052516 9 Fan Motor R03039028206 10 Fan Blade R03019020744 11 Left Panel R01014052510Y 12 Right Panel R01014084434Y 13 Assy Front Panel R01014052512 No Description...

Страница 70: ...67 Exploded View and Part List MWM J 2009 OUTDOOR UNIT MODEL MLC015CR M5LC010 015CR 70024061687 Note All exploded view and part list are subjected to change by the manufacturer without prior notice...

Страница 71: ...11 Left Panel R01014051166Y 12 Right Panel R01014051167Y No Description Part Number 13 Assy Front Panel R01014051171Y 14 Assy Control Panel MLC015CR R50044086062 M5LC010CR R50044086062 M5LC015CR R5004...

Страница 72: ...al www mcquayup com Products manufactured in an ISO certified facility This document contains the most current product information as of this printing For the most up to date product information pleas...