Page 4 / IM 354

CL

5. Complete the electrical work in the subbase and the

junction box.

6. Rough-in the condensate drain (if used) to the left front

side of the subbase. A connection may be made between
this field supplied drain and the condensate drain which
will be installed later at the underside of the wall sleeve.

7. The subbase cavity should be fitted with a piece of 6"

(152mm) fiberglass batting to prevent condensation on
the wall sleeve basepan.

Subbase Installation:
1. The subbase provides a 1

3

16

" (30mm) inset on the sides of

the conditioner. Locate the subbase on the floor and align
its center line with the center line of the wall opening  (see
Figure 5).

2. Determine the depth of the side extension pieces desired

and break at the proper score line. Insert the extension
pieces into the front assembly and secure with two short
screws on each side (see Figure 4).

3. Secure the assembly to the floor.

4. Insert the two leveling bolts into the subbase, one on each

end. Retain the two long screws to secure the wall sleeve
after it is installed.

Optional Louver Frame Installation
Whenever a louver frame is used, it must be installed prior to,
or at the same time as, the room cabinet/wall sleeve. It must
be level and square (see Figure 6).

1. Apply a bead of good caulking compound around the four

inner surfaces of the louver frame vertical flange (see
Figure 7).

2. Insert the sleeve of the louver frame into the wall opening

from the exterior of building and apply firm pressure so the
caulked louver frame vertical flanges are snug against the
exterior building surface.

3. Secure the louver frame to the wall through the sides and

top of the sleeve. Never secure the louver frame  through
the bottom. Note: The louver frame may also be secured
from inside the room cabinet/wall sleeve by screws driven
through the sides and top of the louver frame sleeve.

Pre-Installation Conditioner Preparation
1. Remove the outer carton of the room cabinet/wall sleeve/

chassis package and inspect the conditioner for shipping
damage. Report any damage to the carrier.

2. Save the large inner cardboard liner which can be reused

to cover the installed conditioner until its ready for use. It
is scored, and can be easily folded to the proper depth for
the particular room cabinet exposure into the room.

Room Cabinet/Wall Sleeve Installation

Figure 5.

3. Remove the front panel and filter. Refer to page 7 for

details.

4. Remove the retaining clips at the bottom rear of the

chassis which hold the chassis in place during shipment.

5. Remove the chassis by pulling evenly at the positions

indicated as “Hand Holds” only. Caution: Do not pull on
the evaporator fan housings or control box.

6. Check the nameplate data on the chassis to ensure that

the correct jobsite distribution has been made with re-
spect to the heating and cooling capacities. Corner rooms
normally require larger capacities.

9

16

" (14mm)

Outline of Cabinet/Wall Sleeve

0" to 11

1

4

"

(0 to 286mm)

14 

3

8

"

(365mm)

21

1

4

"

(540mm)

21

1

4

"

(540mm)

4

5

8

"

(117mm)

9

9

16

"

(243mm)

2

9

16

"

(65mm)

Electrical
Junction Box

4

3

8

" (111mm)

1

3

16

" (30mm)

Condensate Drain

Rough-in Area

2

1

2

"

(64mm)

5

8

" (16mm)

3" (76mm)

5"

(127mm)

5"

(127mm)

22

7

8

"

(581mm)

3

1

2

" (89mm)

5

1

2

" (140mm)

Electrical
Rough-in Areas

Top View

Figure 6.

*Outside dimensions

Louver Frame

18

5

8

"

(473mm)

16

5

8

"

(422mm)*

3

3

8

"

(86mm)

1

1

16

"

(2mm)

47

1

8

" (1197mm)

45

1

4

" (1150mm)*

Содержание Incremental MQT Series

Страница 1: ...uh cooling 09 Nominal 9 000 Btuh cooling 11 Nominal 11 000 Btuh cooling 14 Nominal 14 000 Btuh cooling Vintage Designation B Sizes 06 09 11 C Size 14 Unit Type A Air conditioner with electric heat B Air conditioner with hydronic heat C Heat pump with supplemental electric heat MQT 09 B C 5 B Heater Code A 2 0 kW electric heat B 3 2 kW electric heat C 4 8 kW electric heat G Steam heat W Hot water h...

Страница 2: ...onal 3 8 10mm Louver Stamped Standard or 11 8 29mm Louver Extruded Optional 1 2 3 3 1 Note 4 minimum space requirement between underside of unit and floor for return air Subbase is optional on 208 and 230 volt units but standard on 265 volt A 3 4 19mm drip lip Optional condensate connection Figure 2 Conditioner wall mounted 93 4 248mm Min 4 102mm Min 2 x 4 51 x 102mm Junction Box All wiring should...

Страница 3: ... provided in the basepan of the wall sleeve for this purpose Optional Subbase Whenever a subbase is used it must be installed prior to the room cabinet wall sleeve The subbase provided in four pieces is adjustable from 43 8 to 155 8 111 to 397mm in depth to accommodate various projections of the conditioner into the room The standard subbase height is 4 102mm with adjustable leveling bolts to 41 2...

Страница 4: ...r building surface 3 Secure the louver frame to the wall through the sides and top of the sleeve Never secure the louver frame through the bottom Note The louver frame may also be secured from inside the room cabinet wall sleeve by screws driven through the sides and top of the louver frame sleeve Pre Installation Conditioner Preparation 1 Remove the outer carton of the room cabinet wall sleeve ch...

Страница 5: ... wall opening by the depth of the louver to be installed see Figure 8 The center of gravity of the conditioner is 91 2 241mm from the rear face For wall mounted conditioners the center of gravity must be within the load bearing portion of the wall otherwise some method of support is required 3a Installations without a subbase Level or pitch the room cabinet wall sleeve a maximum of1 8 3mm down war...

Страница 6: ...e assembly is 1 2 nominal copper tubing 5 8 O D actual The easiest method of connection would be with a short length of 5 8 I D flexible PVC tubing having a wall thickness of at least 1 8 3mm to prevent kinking or collapse however follow all local applicable codes Heating Cooling Chassis Installation 1 Slide the chassis into the room cabinet wall sleeve until firmly seated against the weather seal...

Страница 7: ...losed exerting sufficient pressure on the top black border area to allow the latching buttons to snap into place usually with an audible click 6 Replace the two sheetmetal screws adjacent to the latch ing buttons in the front panel 7 Replace the filter assembly at the bottom of the front panel Initial start up of the Incremental conditioners by an experi enced technician is usually the responsibil...

Страница 8: ...he original owner for one year Refrigerating circuits consist of the motor compressor assembly evapora tor coil condenser coil and interconnecting tubing Repairs under this warranty will be made at the Company s expense provided that the refrigerating circuit is delivered without shipping damage transportation prepaid to the factory or to a factory designated repair station at the Company s option...

Отзывы: