30
ACZ 010A through 039A
IOMM ACZ1
Compressor Lead/ Lag
The compressor designated as the lead will be the first to start and the last to shut off. Lead/lag
designation is switched based on the number of starts. After 10 starts on Compressor #1 as lead,
Compressor #2 starts as Lead for 10 starts, and then the cycle is repeated.
Capacity Overrides
The following conditions will override the capacity control when the unit is in the COOL mode.
Low Evaporator Pressure
If the unit is running at stage 1 and the evaporator pressure drops below the Low Evaporator
Pressure-Hold setpoint, the unit will hold at stage 1. This condition will inhibit the unit from loading
until the evaporator pressure reaches the hold setpoint plus 8-psi.
If the unit is running at stage 2 and the evaporator pressure drops below the Low Evaporator
Pressure-Unload setpoint, the unit will unload to stage 1. This condition will inhibit the unit from
loading until the evaporator pressure reaches the hold setpoint plus 10 psi.
Discharge Pressure Stage Down
If the unit is running at stage 2 and the condenser pressure rises above the High Condenser Pressure
Stage Down setpoint, the unit will unload to stage 1. This condition will inhibit the unit from loading
until the condenser pressure drops below the unload setpoint less 100 psi.
Digital Output Control
Each digital output is controlled according to the following rules and in accordance with whether the
unit is in normal operation or TEST (test mode). All outputs are initialized to OFF at power on.
Alarm –
(Terminals J12 – NO1)
This output is turned ON when any “EQUIPMENT PROTECTION ALARMS” occur. It is turned
OFF when all alarms have been cleared.
Liquid Line Solenoid –
(Terminals J12 – NO3)
This output is ON when the Compressors are ON. It is OFF for all other cases.
Motor Control Relay #1, #2
– (Terminals J13 – NO4, J13 – NO5)
This output is ON when the Compressors are ON. It is OFF for all other cases.
Fan #1, #2, & #3
– (Terminals J13 – NO6, J14 – NO7, J15 – NO8)
Condenser Fans Staging is based on Condenser pressure as selected Fan Stage On & Off setpoints.