IOMM ACZ1
ACZ 010A through 039A
27
Table 10, Setpoints
Description
Default
Range
PW
Unit
Unit Enable
OFF
OFF, ON
O
Available Mode
COOL
COOL
TEST
M
Control Source
SWITCHES
SWITCHES, KEYPAD,
NETWORK
O
Display Units
°
F/psi
°
F/psi
O
Language
ENGLISH
ENGLISH,
O
BAS Protocol
None
None, BACnet, L
ON
W
ORKS
M
* Condenser Fans Stages
2
2,3
M
* Phase Voltage Protection
N
N,Y
M
* SpeedTrol Option
N
N,Y
M
Staging
Stage Up Delay
120
20 to 240 sec
M
Stage Down Delay
30
10 to 60 sec
M
Timers
Evap Flow/Air Flow Proof
5 sec
3 to 120 sec
M
Low Evap Pressure Delay
60 sec
10 sec to 120 sec
M
Start-Start
15 min
10 to 60 min
M
Stop-Start
5 min
3 to 20 min
M
Alarms
Low Evap Pressure
58 psi
30 to 60 psi
M
Low Evap Pressure-Hold
59 psi
31 to 65 psi
M
Low Evap Pressure-Unload
59 psi
31 to 65 psi
M
High Condenser Stage Down
370 psi
365 to 375 psi
M
High Condenser Pressure
380 psi
380 to 390 psi
M
* Low Ambient Lockout
35.0
°
F
–2 to 60
°
F
M
Condenser Fans
Fan Stages
2
2-3
M
Stage #1 On
150psi
140 to 200 psi
M
Stage #2 On
290 psi
230 to 330 psi
M
Stage #3 On
310 psi
230 to 330 psi
M
Stage #1 Off
Off
Off with Stage #1
M
Stage #2 Off
170 psi
150 to 200 psi
M
Stage #3 Off
180 psi
150 to 200 psi
M
(*) These items are factory set prior to shipment.
Equipment Protection Alarms
Equipment protection alarms execute rapid compressor shutdown.
The following table identifies each equipment protection alarm, gives the condition that causes the
alarm to occur, and states the action taken because of the alarm. If the alarm is auto-clearing, the
reset condition is shown below. Otherwise, the alarm is manually reset, requiring the operator to clear
the alarm.