Vibration Isolators
Vibration isolators are recommended for all roof-mounted installations or wherever vibration
transmission is a consideration. The isolators can be purchased from McQuay by the part numbers
shown in the table.
The unit should be initially on shims or blocks at the listed free height. When all piping, wiring,
flushing, charging, etc. is completed, the springs are adjusted upward to loosen the blocks or shims
that are then removed.
A rubber anti-skid pad is part of the isolator. Installation of spring isolators requires flexible piping
connections and at least three feet of flexible conduit to avoid straining the piping and transmitting
vibration and noise.
Table 1, Recommended Vibration Isolators
ACZ UNIT
ISOLATOR
TYPE
ISOLATOR
PART NO.
NUMBER
REQUIRED
KIT of FOUR
PART NO.
LOCATION
ISOLATOR
DESCRIPTION
021639703
2
LF, RF
RP-3 Green
010A – 039A
Rubber-in-Shear
021639701
2
350014857
LB, RB
RP-3 Red
010A – 020A
Spring Isolators
047792726
4
350014835
All
CP-1-26
047792726
2
LF, RF
CP-1-27
025A – 039A
Spring Isolators
047792727
2
350014839
LB, RB
CP-1-26
Note: See dimension drawing for location of isolators
Corner Operating Weights
ACZ
Unit
Model
RF
LF
RB
LB
Total
010
309
311
190
190
1000
013
309
311
190
190
1000
016
402
404
207
207
1220
020
511
513
158
158
1340
025
492
494
242
242
1470
028
498
501
245
246
1490
033
614
567
302
277
1760
039
683
630
336
311
1960
Chilled Water System
Water Piping (Applicable when the Unit is Field Connected to a Water
Type Evaporator)
Local authorities can supply the installer with the proper building and safety codes required for proper
installation.
Install piping with minimum bends and changes in elevation to minimize pressure drop. Consider the
following when installing water piping:
1.
Vibration eliminators to reduce vibration and noise transmission to the building.
2.
Shutoff valves to isolate the unit from the piping system during unit servicing.