WARNING
The hot gas line can become hot enough to cause injury in a very short time. Do not allow
prolonged contact during valve checkout.
On installations where the condensing unit is remote from the evaporator, it is recommended that the
hot gas bypass valve be mounted near the condensing unit to minimize the amount of refrigerant that
will condense in the hot gas line during periods when hot gas bypass is not required.
Figure 13, Hot Gas Bypass Piping
Discharge
Line
Hot Gas
Bypass Valve
Hot Gas Bypass
Solenoid Valve
Suction Line
Adjustable
Remote Bulb
External Equalizer
Connection to Suction
Side of Evaporator
To Evaporator Inlet
After Expansion Valve
Figure 14, Hot Gas Bypass Adjustment
80
70
60
50
40
30
30
40
50
60
70
80
90
100
110
MINIMU
M
MAXIM
UM
FACTO
RY SET
TING
V
A
L
VE OPEN
IN
G PR
ESSU
R
E
(
PSI
G)
REMOTE BULB ADJUSTMENT RANGE
TEMP (°F) AT BULB LOCATION
AD
J
U
ST
M
E
N
T
RANGE